Why data centers use liquid coolant

How computer cooling changed, what propylene glycol does, and what we can learn from past leaks.

Michael Bommarito · November 14, 2026 · Research guide

Why this matters

More powerful chips put more heat in a smaller space.

AI servers pack powerful processors into tightly filled racks. Liquid cooling carries heat away from those processors through pipes. Some systems use a mixture of water and propylene glycol, often called PG25. The liquid keeps circulating while outdoor equipment releases the heat.

This design can save water by avoiding cooling towers that lose water to evaporation. It also brings large amounts of coolant into buildings and across equipment. The fluid, the pipes, and the plan for handling leaks all deserve attention.

NVIDIA’s rack design · Oracle’s cooling system · EPA’s study of glycol runoff

Cooling has a historyEngineers have used liquid to cool computers for decades. AI is expanding its use.
PG25A coolant with roughly 25% propylene glycol, mixed with water and additives that protect the equipment.
Follow the pipesHow much can leak, how quickly valves close, and where drains lead help determine the damage.

01 · How we got here

Computer cooling has moved closer to the chips.

First, move the heat out of the room.

A computer produces heat as it uses electricity. Fans push air over its hot parts, and the warm air has to go somewhere. In a conventional data center, air-conditioning equipment cools the air and sends it back through rows of servers. Operators arrange the racks and separate hot and cool aisles to keep warm exhaust air from flowing back into server intakes. DOE design guide, §§4–5

The heat then has to leave the building. Some systems use cooling towers, where part of the water evaporates and carries heat away. Others release heat through outdoor coils and fans. These choices affect both water use and electricity use. DOE cooling guide

Liquid cooling goes back to mainframes.

IBM introduced a water-cooled computer product in 1964. Water cooled heat exchangers between stacks of circuit boards. The following year, IBM added a cooling distribution unit to control the quality of the water supplied to the computer. In his 2005 history of the technology, IBM engineer Roger Schmidt described how other mainframe manufacturers also adopted water cooling over the following decades. Schmidt, 2005

In the 1990s, a shift to lower-power chip designs made air cooling a cheaper choice for many systems. As chip power rose again, manufacturers brought liquid cooling back. IBM’s 2005 design put a water-cooled heat exchanger on the back of a server rack, close to the hot exhaust air. The recurring problem was how to remove more heat from limited space. History of liquid cooling

AI puts that problem into a single rack.

Modern AI systems group many graphics processing units, or GPUs, so they can work together on a model. NVIDIA’s GB200 NVL72 design connects 72 GPUs in one rack. NVIDIA described a cooling requirement of 120 kilowatts for that rack in 2024. That is a concentrated heat load for equipment occupying a small patch of floor. NVIDIA, October 2024

Liquid can collect heat at the processor and carry it through pipes, reducing the work of moving air through crowded equipment. In direct-to-chip cooling, coolant flows through a metal plate attached to a hot component. The plate conducts heat into the moving liquid. DOE identifies rising processor power as a reason for wider adoption of this approach. DOE §5.6

That history explains why data centers use liquid cooling: it helps engineers fit and operate more powerful computers in a given space. Communities then need to understand how the chosen system uses water and handles its coolant.

02 · How the system works

What is in the coolant, and where does it go?

PG stands for propylene glycol. Mixed with water, it lowers the fluid’s freezing point. Dow sells a PG25 coolant for direct-to-chip systems with freeze protection down to −10°C (14°F). Its additives help prevent corrosion and keep the fluid’s chemistry stable as it moves through metal parts, hoses, seals, and pumps. Dow Dow

NVIDIA’s Q32xx/Q34xx switch manual calls for a fill of 25% PG and 75% water. Suppliers make products for these equipment requirements. In November 2026, Dynalene announced that its PG-D25 coolant had qualified under NVIDIA’s DSX Ready program. NVIDIA Dynalene announcement

For a particular facility, the product name, supplier’s specifications, and safety data sheet provide the starting point. They describe the fluid’s concentration, hazards, and handling requirements. Details about additives and long-term performance may require further information from the supplier.

Propylene glycol

The PG in PG25. It is also permitted in certain foods under FDA rules.

Ethylene glycol

A different chemical used in some antifreeze and deicing products. Historical spill records may name either glycol or a mixture.

Glycol ethers

A separate family of chemicals, including some in the 2014 Elk River spill. Identifying the chemical is essential when comparing incidents.

FDA food-use rule · Airport deicing chemicals · Elk River investigation

Heat often passes through two separate loops.

One loop carries liquid through the cold plates attached to the server components. It returns to a coolant distribution unit, usually shortened to CDU. Inside that unit, a heat exchanger passes the heat to a second loop that serves the building. The fluids stay in their own pipes. Each loop needs a fluid that works with its equipment and materials. Open Compute Project guidance

Server loopChips → cold plates → CDU

Coolant picks up heat at the equipment.

Heat exchangerHeat moves between the two loops.
Building loopCDU → outdoor cooling → CDU

A second fluid carries heat out of the building.

This common layout shows the two loops. Saline’s construction drawings would show its pipe routes, equipment, and fluid volumes.

Oracle describes an outdoor cooling arrangement much like a car radiator: fans blow air across coils, the liquid gives up heat, and the cooled liquid returns through the pipes. Because the cooling process keeps reusing the liquid, it avoids the continuing evaporation losses of a cooling tower. Oracle / Travis Grizzel

03 · Saline Township

Oracle has described the design. The fluid details still need documentation.

Oracle says the Saline project will use a closed-loop, non-evaporative system: fill the pipes, circulate the liquid, and release heat through outdoor equipment. Its February 2026 explanation says top-offs should be rare and tied to abnormal conditions. Oracle Oracle / Travis Grizzel

What we know so far

The cooling design
Oracle describes a system that reuses its coolant and avoids evaporation during cooling.
A documented coolant option
NVIDIA specifies PG25 for named equipment. Confirming Saline’s choice requires its equipment and fluid purchase records.
The details to obtain
The supplier, product, additives, amount of liquid in each loop, maintenance plan, and amount that could escape during a break.

The amount of coolant depends on the size and length of pipes, the equipment they connect, storage tanks, and how much of the campus has been built. A facility’s electrical capacity tells us too little to calculate that volume reliably.

For leak planning, a useful number is how much fluid could escape before valves close and pumps stop. The answer depends on which pipes and tanks remain connected to the break. Drawings of the installed system, fill records, and valve controls would allow an engineer to calculate it.

04 · Effects on water

Breaking down glycol uses oxygen that fish need.

FDA permits propylene glycol in foods under rules covering purity, uses, and amounts. Environmental review asks a different question: what happens when a quantity of industrial coolant reaches soil or water? The full mixture and the amount released both matter. 21 CFR 184.1666

Microorganisms consume oxygen as they break down glycol in water. A large enough release can lower the dissolved oxygen available to fish and other aquatic life. EPA documented this problem in its study of airport deicing runoff, along with effects from additives in deicing products. US EPA

Other chemicals can also consume oxygen. A 2025 study by USGS researchers used measurements from Milwaukee airport runoff collected between 2005 and 2022 to estimate the contributions from PG and acetate. Testing for the individual chemicals helps explain where the oxygen demand comes from. LaFond-Hudson et al., 2025

How much oxygen can glycol use?

The chemistry gives us a starting estimate. Completely breaking down one milligram of PG into carbon dioxide and water requires about 1.68 milligrams of oxygen. Engineers call this theoretical oxygen demand. EPA calculates it from the reaction C₃H₈O₂ + 4 O₂ → 3 CO₂ + 4 H₂O. EPA, Table 9-4

Try the calculation

Compare the oxygen needed with the oxygen in the water.

Enter the PG concentration after a release has mixed into water. The unit mg/L means milligrams per litre.

8.41 mg/L oxygen needed for complete breakdown — 105% of the oxygen present at the start.

In this example, 5 mg/L of PG would need about 8.4 mg/L of oxygen to break down completely. The water starts with 8 mg/L. An actual stream also gains oxygen from the air, dilutes the spill as water flows, and contains other materials that use oxygen. Temperature and microbial activity affect how quickly breakdown happens. Predicting effects on fish requires those conditions as well as the chemistry.

Laboratories measure oxygen demand in several ways. BOD₅ measures how much oxygen biological activity uses over five days under test conditions. COD uses a chemical test. The theoretical calculation estimates the oxygen needed for complete breakdown. Comparing results requires matching the test and the concentration of the fluid.

For a particular creek or river, the assessment starts with the amount that could spill and the route it would take. Valves can limit the amount released. Collection areas can hold spilled fluid for recovery. A drain leading straight to a creek gives the fluid a route around treatment.

05 · Past incidents

What has happened when cooling and glycol systems leaked?

The incidents below show several ways liquid can escape: a pipe leaks underground, a worker empties a drum into a drain, or pond water is released through a valve. Their usefulness depends on the chemical involved, the equipment, and where the liquid went. Estimating how often a new facility might spill would require a much broader set of operating records.

Reported in November 2026

Ascent TOR1, Cambridge, Ontario

Related Digital told CityNews that a spill occurred at its Ascent TOR1 data center on July 2. The company described 5,000 litres of a mixture containing 25% propylene glycol and 75% water, and said it reported and contained the spill. CityNews, November 11

On July 19, a separate report concerned a milky, foul-smelling substance in a stormwater pond. Related Digital says the two events were unrelated. A ministry spokesperson later said samples showed no contaminants of concern and that the owner had reported and addressed both incidents. Company statements Ministry response, reported November 13

The company has acknowledged a PG-mixture spill at an operating data center. The later pond event remains a separate question. We have the reported company and ministry statements; assessing the connection would require the spill file and full laboratory results, including when and where samples were taken.

Propylene glycol · EPA cleanup report

Fred Meyer distribution center

Clackamas, Oregon · August 2014

A contractor working on the building’s sprinkler system collected used propylene glycol in drums, then emptied about 120 US gallons into a storm drain. Some reached Carli Creek. EPA’s final report describes the cleanup and water sampling.

The incident shows how routine maintenance can send fluid into a waterway. Workers need to know where drains lead and how to collect used liquid.

One early creek sample contained 6.37 mg/L of PG. Four other samples were below the laboratory’s reporting limit of 5 mg/L. Those results leave the amount below that limit unknown. EPA reported that cleanup was complete.

US EPA Region 10

Deicing runoff · Justice Department record

Detroit Metropolitan Airport

Romulus, Michigan · May 2001; guilty plea June 2006

Airport personnel opened valves that released roughly 25 million gallons of pond water into the Frank and Poet Drain. The ponds held runoff from deicing products, including ethylene glycol and propylene glycol. Investigators found the discharge while looking into a fish kill.

Collection ponds depend on working treatment connections and control over the valves that release their water. This case also shows the importance of reporting a discharge.

The 25-million-gallon figure describes pond water containing deicing material. In 2006, the Airport Authority pleaded guilty to negligently failing to report the discharge.

US Department of Justice

Propylene glycol · city updates

Glens Falls Recreation Center ice rink

Glens Falls, New York · 2025

Employees noticed the coolant level falling in January. The city identified propylene glycol in March. In October, it reported that testing found glycol in soil and groundwater beneath the building. After temporary repairs, the city said the system was holding its fluid.

Checking fluid levels can reveal a hidden leak. The city then needed to locate the contamination, check the repairs, and plan longer-term work on its aging cooling system.

The city said testing showed the contamination stayed beneath the building. The case concerns an older ice-rink system and gives a concrete example of the work required after an underground coolant leak.

City of Glens Falls (2025-03-25) · City of Glens Falls (2025-10-31)

Water leak · Google incident report

Google Cloud Paris region

Paris, France · April 25–26, 2023

Water entered Google’s space from another room above its equipment. A battery room flooded and caught fire, equipment shut down, and recovery required extensive cleaning.

A leak above electrical equipment can spread damage across a building. Google’s follow-up work included reviewing water routes and considering drip trays.

Google describes water in its report and leaves its chemical composition unspecified. The incident illustrates how liquid can damage equipment and interrupt service.

Google Cloud

The 2014 Freedom Industries spill into West Virginia’s Elk River involved crude MCHM and polyglycol ethers, chemicals used in coal processing. The Chemical Safety Board’s investigation describes tank corrosion and failed containment. Those findings are relevant to storage design. Comparing the spill’s health effects with PG25 requires accounting for the different chemicals. CSB investigation

06 · Keeping the system working

Check the fluid, track losses, and plan for repairs.

The Open Compute Project recommends checking glycol concentration and pH every quarter and recording the results. It also discusses annual laboratory testing where needed. Results outside the supplier’s acceptable ranges can lead to adjustment or replacement of the fluid. The equipment requirements, supplier’s advice, and test results guide the replacement schedule. OCP §§5–6

Operators can track how much liquid they add and compare that with service records. An unexplained fall in fluid level calls for investigation. Repairs may require draining part of a loop, replacing a component, collecting the old liquid, and refilling the pipes. Workers need the right containers and a clear disposal route before they start.

Manufacturers build safeguards into some equipment. IBM’s 9175 system includes drip trays, low-fluid warnings, pump leak sensors, and a spill kit. A site review should identify which safeguards its equipment provides and how staff will respond to them. IBM §3.3

Delivery, initial filling, maintenance, and final removal each involve handling liquid outside normal operation. For each step, the plan should name the person responsible, explain how to stop a spill, and show where the collected fluid will go.

07 · Michigan rules

Water protection and waste rules apply to coolant handling.

Protecting waterways. Michigan law prohibits direct or indirect discharges of substances that are or may become harmful to state waters and their uses, including aquatic life. MCL 324.3109(1)

Stormwater permits. EGLE considers the facility’s activities, whether rain can reach industrial materials, and where runoff goes when deciding which industrial stormwater requirements apply. The site’s permit and drainage plan show what discharges are allowed. Construction and operating permits need to be checked for their respective requirements. EGLE guidance

Used coolant. EGLE says used antifreeze can be hazardous or non-hazardous depending on its condition and contents. Michigan offers several ways to manage it, including rules for hazardous waste, universal waste, and non-hazardous liquid industrial by-products. The operator must identify the waste and follow the handling and transport rules for the chosen route. EGLE §2.7.15

Spill plans. Federal Spill Prevention, Control, and Countermeasure rules, known as SPCC, cover oils. A data center’s diesel fuel may fall under those rules. Coolant needs its own assessment of storage, leak control, and recovery. EPA’s description of SPCC

Lessons from airports. The federal airport deicing rule applies to airport operations. Its treatment requirements grew out of experience with glycol runoff. For a data center, the applicable laws, permits, and site conditions determine the requirements. 40 CFR 449.1

08 · Questions for a proposed facility

Ask for details that can be checked.

These questions can help residents, local officials, and engineers review a proposal. Some answers come from permits; others require construction drawings, supplier documents, or operating plans.

  1. What fluid will the facility use?

    Ask for the product name, supplier, safety data sheet, additives, and glycol concentration for each loop. The supplier should explain whether the percentage is measured by weight or by volume.

  2. How much could escape from a break?

    Ask how much coolant each part of the system holds, which valves can close it off, and how quickly they close. Include tanks and pumps that could keep feeding liquid into a broken pipe.

  3. Where would a spill go?

    Trace the drains from roofs, equipment rooms, yards, and delivery areas. Ask how the site would hold spilled coolant, including during rain or firefighting, and how workers would remove it.

  4. How will staff find a leak?

    Ask about fluid-level and leak alarms, records of added coolant, automatic shutdowns, alarm testing, and who responds when an alarm sounds.

  5. What happens during maintenance?

    Ask how the fluid will be tested, when it will be replaced, how workers will collect it, and which recycler or disposal facility will receive it. Any proposed sewer disposal needs acceptance from the sewer authority.

  6. How will effects on nearby water be checked?

    Ask how groundwater flow and surface drainage affect the sampling plan. The plan should explain what will be measured, where and when samples will be taken, how small an amount the laboratory can detect, and who acts on the results.

With those answers, a community can evaluate the water savings, understand what a leak could affect, and see how the operator plans to prevent and handle one.

Sources checked November 14, 2026

Read the original documents.

The sources include equipment manuals, a history by an IBM engineer, government design guides, incident reports, laws, and research. Each entry identifies the publisher and the relevant passage. The Cambridge entries link to reporting of company and ministry statements.

Download the source list (JSON)

  1. Operator statement
    Saline Township Data Centers

    Oracle · Checked 2026-11-14
    Where to look: Water tab
    Oracle’s description of the cooling system planned for Saline Township.

  2. Operator statement
    Closed-loop cooling in Oracle AI data centers

    Oracle / Travis Grizzel · 2026-02-09 · Checked 2026-11-14
    Where to look: Direct-to-chip; Proven design
    How Oracle expects its cooling system to work, including filling and occasional top-offs.

  3. Manufacturer documentation
    Q32xx and Q34xx XDR switch systems user manual

    NVIDIA · Checked 2026-11-14
    Where to look: §3.14.2.2.2, PG25 Fill
    Coolant requirements for the named NVIDIA switches.

  4. Manufacturer announcement
    Dynalene PG-25 Qualifies as an NVIDIA DSX Ready Coolant Solution

    Dynalene · 2026-11-02 · Checked 2026-11-14
    Where to look: Announcement; qualification scope
    Dynalene’s announcement that PG-D25 qualified under NVIDIA’s DSX Ready program.

  5. Industry guidance
    Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Single-Phase Cold Plate-Based Liquid Cooled Racks

    Open Compute Project · Checked 2026-11-14
    Where to look: §§4–6; printed pp. 11, 17–20
    Choosing fluids that work with the equipment, checking fluid condition, and maintaining the system.

  6. Manufacturer documentation
    DOWFROST LC 25 Heat Transfer Fluid

    Dow · Checked 2026-11-14
    Where to look: Overview; benefits
    A commercial PG25 coolant, its corrosion protection, and its freeze protection.

  7. Manufacturer documentation
    Propylene Glycols: Data Centers

    Dow · Checked 2026-11-14
    Where to look: Data Centers
    The roles of corrosion inhibitors, pH buffers, and stabilizers in Dow’s coolant products.

  8. Regulation
    21 CFR 184.1666: Propylene glycol

    eCFR / FDA · Checked 2026-11-14
    Where to look: §184.1666(b)–(d)
    Requirements for using propylene glycol as a food ingredient.

  9. Agency technical report
    Airport Deicing Technical Development Document

    US EPA · 2012-04 · Checked 2026-11-14
    Where to look: §9; Table 9-4 (printed p. 100)
    The chemical calculation of oxygen needed to break down deicing chemicals.

  10. Agency technical report
    Environmental Impact and Benefit Assessment: Airport Deicing

    US EPA · 2012-04 · Checked 2026-11-14
    Where to look: §1.4, printed p. 1-5
    Effects of deicing runoff on oxygen levels and aquatic life.

  11. Original research
    Apportionment of oxygen demand contributions from aircraft and pavement deicer freezing point depressants in airport runoff, Milwaukee, Wisconsin, 2005–2022

    LaFond-Hudson, Corsi & Rutter (USGS) · 2025-01-06 · Checked 2026-11-14
    Where to look: Abstract; Results and discussion; DOI 10.1093/inteam/vjae047
    Measurements of airport runoff and estimates of the oxygen demand from PG and acetate.

  12. Agency incident report
    Fred Meyer Propylene Glycol Spill: Final POLREP #2

    US EPA Region 10 · 2014-08-27 · Checked 2026-11-14
    Where to look: §§1.1.3, 2.1.2
    A contractor’s disposal of about 120 gallons into a storm drain, followed by creek sampling and cleanup.

  13. Agency enforcement announcement
    Wayne County Airport Authority Pleads Guilty to Violation of Clean Water Act

    US Department of Justice · 2006-06-08 · Checked 2026-11-14
    Where to look: Guilty plea; May 16–17, 2001 discharge
    The Airport Authority’s guilty plea for failing to report a discharge of pond water containing deicing runoff.

  14. Municipal incident statement
    City cooperates with NYS DEC regarding ice rink

    City of Glens Falls · 2025-03-25 · Checked 2026-11-14
    Where to look: Full release
    The falling fluid level, identification of PG, and the investigation then underway.

  15. Municipal incident update
    Glens Falls Rec Center to Open for Hockey Saturday, Nov. 1

    City of Glens Falls · 2025-10-31 · Checked 2026-11-14
    Where to look: Sampling; temporary repairs
    Results from sampling beneath the building and the city’s account of temporary repairs.

  16. Operator incident report
    Europe-west9 service incident: water leak, mitigation and prevention

    Google Cloud · 2023-04-25 · Checked 2026-11-14
    Where to look: Water Leak, Mitigation, and Prevention
    Google’s account of a water leak, battery-room fire, service interruptions, and recovery work.

  17. Original reporting of company statements
    Spill at Cambridge data centre unrelated to milky algae bloom in stormwater pond

    CityNews Kitchener / Erin Anderson · 2026-11-11 · Checked 2026-11-14
    Where to look: Related Digital statements
    Related Digital’s account of the July 2 spill and its position on the later pond event, reported by CityNews.

  18. Original reporting of ministry statements
    Ministry insists no contaminants of concern were identified in data centre spill

    CambridgeToday / Doug Coxson, via The Trillium · 2026-11-13 · Checked 2026-11-14
    Where to look: Ministry response
    A ministry spokesperson’s response about sampling and the owner’s handling of the two events.

  19. Statute
    MCL 324.3109: Discharge into state waters

    Michigan Legislature · Checked 2026-11-14
    Where to look: §3109(1)
    Michigan’s prohibition on discharges that harm or may harm state waters and their uses.

  20. Agency guidance
    Industrial Stormwater Program

    Michigan EGLE · Checked 2026-11-14
    Where to look: Permit information; no exposure
    How EGLE decides which industrial stormwater requirements apply to a facility.

  21. Agency guidance
    Michigan Guide to Environmental Regulations, Chapter 2: Waste Materials Management

    Michigan EGLE · Checked 2026-11-14
    Where to look: §2.7.15, Spent Antifreeze
    Options for handling used antifreeze under Michigan waste rules.

  22. Agency guidance
    SPCC Rule regulated oil types

    US EPA · Checked 2026-11-14
    Where to look: Oil definition
    The types of oil covered by federal SPCC rules.

  23. Regulation
    40 CFR Part 449: Airport Deicing Point Source Category

    eCFR / US EPA · Checked 2026-11-14
    Where to look: §449.1
    The operations covered by the federal airport deicing rule.

  24. Manufacturer documentation
    IBM Z and IBM LinuxONE: 9175 Internal Water Cooling System

    IBM · 2025 · Checked 2026-11-14
    Where to look: §3.3, printed p. 9
    Drip trays, fluid-level warnings, leak sensors, and spill equipment in IBM’s 9175 system.

  25. Agency investigation
    Freedom Industries Chemical Release: final investigation

    US Chemical Safety Board · 2017-05 · Checked 2026-11-14
    Where to look: Executive summary
    The chemicals released, tank corrosion, and failed containment at Freedom Industries.

  26. History by an IBM engineer
    Liquid Cooling is Back

    Roger R. Schmidt / Electronics Cooling · 2005-08-01 · Checked 2026-11-14
    Where to look: Historical Perspective; introduction
    IBM’s water-cooled systems from 1964, the shift toward air cooling, and a return to rack heat exchangers in 2005.

  27. Manufacturer design explanation
    NVIDIA Contributes NVIDIA GB200 NVL72 Designs to Open Compute Project

    NVIDIA / Amr Elmeleegy · 2024-10-15 · Checked 2026-11-14
    Where to look: Meeting data center compute demands; liquid cooling design
    72-GPU rack and its 120 kW cooling requirement.

  28. Government design guide
    Best Practices Guide for Energy-Efficient Data Center Design

    US Department of Energy / NREL · 2024-07 · Checked 2026-11-14
    Where to look: §4 Air Management; §5 Cooling Systems, especially §5.6
    Airflow, building cooling systems, and the reasons for bringing liquid cooling to processors.