01 · How we got here
Computer cooling has moved closer to the chips.
First, move the heat out of the room.
A computer produces heat as it uses electricity. Fans push air over its hot parts, and the warm air has to go somewhere. In a conventional data center, air-conditioning equipment cools the air and sends it back through rows of servers. Operators arrange the racks and separate hot and cool aisles to keep warm exhaust air from flowing back into server intakes. DOE design guide, §§4–5
The heat then has to leave the building. Some systems use cooling towers, where part of the water evaporates and carries heat away. Others release heat through outdoor coils and fans. These choices affect both water use and electricity use. DOE cooling guide
Liquid cooling goes back to mainframes.
IBM introduced a water-cooled computer product in 1964. Water cooled heat exchangers between stacks of circuit boards. The following year, IBM added a cooling distribution unit to control the quality of the water supplied to the computer. In his 2005 history of the technology, IBM engineer Roger Schmidt described how other mainframe manufacturers also adopted water cooling over the following decades. Schmidt, 2005
In the 1990s, a shift to lower-power chip designs made air cooling a cheaper choice for many systems. As chip power rose again, manufacturers brought liquid cooling back. IBM’s 2005 design put a water-cooled heat exchanger on the back of a server rack, close to the hot exhaust air. The recurring problem was how to remove more heat from limited space. History of liquid cooling
AI puts that problem into a single rack.
Modern AI systems group many graphics processing units, or GPUs, so they can work together on a model. NVIDIA’s GB200 NVL72 design connects 72 GPUs in one rack. NVIDIA described a cooling requirement of 120 kilowatts for that rack in 2024. That is a concentrated heat load for equipment occupying a small patch of floor. NVIDIA, October 2024
Liquid can collect heat at the processor and carry it through pipes, reducing the work of moving air through crowded equipment. In direct-to-chip cooling, coolant flows through a metal plate attached to a hot component. The plate conducts heat into the moving liquid. DOE identifies rising processor power as a reason for wider adoption of this approach. DOE §5.6
That history explains why data centers use liquid cooling: it helps engineers fit and operate more powerful computers in a given space. Communities then need to understand how the chosen system uses water and handles its coolant.
02 · How the system works
What is in the coolant, and where does it go?
PG stands for propylene glycol. Mixed with water, it lowers the fluid’s freezing point. Dow sells a PG25 coolant for direct-to-chip systems with freeze protection down to −10°C (14°F). Its additives help prevent corrosion and keep the fluid’s chemistry stable as it moves through metal parts, hoses, seals, and pumps. Dow Dow
NVIDIA’s Q32xx/Q34xx switch manual calls for a fill of 25% PG and 75% water. Suppliers make products for these equipment requirements. In November 2026, Dynalene announced that its PG-D25 coolant had qualified under NVIDIA’s DSX Ready program. NVIDIA Dynalene announcement
For a particular facility, the product name, supplier’s specifications, and safety data sheet provide the starting point. They describe the fluid’s concentration, hazards, and handling requirements. Details about additives and long-term performance may require further information from the supplier.
Propylene glycol
The PG in PG25. It is also permitted in certain foods under FDA rules.
Ethylene glycol
A different chemical used in some antifreeze and deicing products. Historical spill records may name either glycol or a mixture.
Glycol ethers
A separate family of chemicals, including some in the 2014 Elk River spill. Identifying the chemical is essential when comparing incidents.
FDA food-use rule · Airport deicing chemicals · Elk River investigation
Heat often passes through two separate loops.
One loop carries liquid through the cold plates attached to the server components. It returns to a coolant distribution unit, usually shortened to CDU. Inside that unit, a heat exchanger passes the heat to a second loop that serves the building. The fluids stay in their own pipes. Each loop needs a fluid that works with its equipment and materials. Open Compute Project guidance
Coolant picks up heat at the equipment.
A second fluid carries heat out of the building.
Oracle describes an outdoor cooling arrangement much like a car radiator: fans blow air across coils, the liquid gives up heat, and the cooled liquid returns through the pipes. Because the cooling process keeps reusing the liquid, it avoids the continuing evaporation losses of a cooling tower. Oracle / Travis Grizzel
03 · Saline Township
Oracle has described the design. The fluid details still need documentation.
Oracle says the Saline project will use a closed-loop, non-evaporative system: fill the pipes, circulate the liquid, and release heat through outdoor equipment. Its February 2026 explanation says top-offs should be rare and tied to abnormal conditions. Oracle Oracle / Travis Grizzel
What we know so far
- The cooling design
- Oracle describes a system that reuses its coolant and avoids evaporation during cooling.
- A documented coolant option
- NVIDIA specifies PG25 for named equipment. Confirming Saline’s choice requires its equipment and fluid purchase records.
- The details to obtain
- The supplier, product, additives, amount of liquid in each loop, maintenance plan, and amount that could escape during a break.
The amount of coolant depends on the size and length of pipes, the equipment they connect, storage tanks, and how much of the campus has been built. A facility’s electrical capacity tells us too little to calculate that volume reliably.
For leak planning, a useful number is how much fluid could escape before valves close and pumps stop. The answer depends on which pipes and tanks remain connected to the break. Drawings of the installed system, fill records, and valve controls would allow an engineer to calculate it.
04 · Effects on water
Breaking down glycol uses oxygen that fish need.
FDA permits propylene glycol in foods under rules covering purity, uses, and amounts. Environmental review asks a different question: what happens when a quantity of industrial coolant reaches soil or water? The full mixture and the amount released both matter. 21 CFR 184.1666
Microorganisms consume oxygen as they break down glycol in water. A large enough release can lower the dissolved oxygen available to fish and other aquatic life. EPA documented this problem in its study of airport deicing runoff, along with effects from additives in deicing products. US EPA
Other chemicals can also consume oxygen. A 2025 study by USGS researchers used measurements from Milwaukee airport runoff collected between 2005 and 2022 to estimate the contributions from PG and acetate. Testing for the individual chemicals helps explain where the oxygen demand comes from. LaFond-Hudson et al., 2025
How much oxygen can glycol use?
The chemistry gives us a starting estimate. Completely breaking down one milligram of PG into carbon dioxide and water requires about 1.68 milligrams of oxygen. Engineers call this theoretical oxygen demand. EPA calculates it from the reaction C₃H₈O₂ + 4 O₂ → 3 CO₂ + 4 H₂O. EPA, Table 9-4
Try the calculation
Compare the oxygen needed with the oxygen in the water.
Enter the PG concentration after a release has mixed into water. The unit mg/L means milligrams per litre.
8.41 mg/L oxygen needed for complete breakdown — 105% of the oxygen present at the start.
In this example, 5 mg/L of PG would need about 8.4 mg/L of oxygen to break down completely. The water starts with 8 mg/L. An actual stream also gains oxygen from the air, dilutes the spill as water flows, and contains other materials that use oxygen. Temperature and microbial activity affect how quickly breakdown happens. Predicting effects on fish requires those conditions as well as the chemistry.
Laboratories measure oxygen demand in several ways. BOD₅ measures how much oxygen biological activity uses over five days under test conditions. COD uses a chemical test. The theoretical calculation estimates the oxygen needed for complete breakdown. Comparing results requires matching the test and the concentration of the fluid.
For a particular creek or river, the assessment starts with the amount that could spill and the route it would take. Valves can limit the amount released. Collection areas can hold spilled fluid for recovery. A drain leading straight to a creek gives the fluid a route around treatment.
05 · Past incidents
What has happened when cooling and glycol systems leaked?
The incidents below show several ways liquid can escape: a pipe leaks underground, a worker empties a drum into a drain, or pond water is released through a valve. Their usefulness depends on the chemical involved, the equipment, and where the liquid went. Estimating how often a new facility might spill would require a much broader set of operating records.
Reported in November 2026
Ascent TOR1, Cambridge, Ontario
Related Digital told CityNews that a spill occurred at its Ascent TOR1 data center on July 2. The company described 5,000 litres of a mixture containing 25% propylene glycol and 75% water, and said it reported and contained the spill. CityNews, November 11
On July 19, a separate report concerned a milky, foul-smelling substance in a stormwater pond. Related Digital says the two events were unrelated. A ministry spokesperson later said samples showed no contaminants of concern and that the owner had reported and addressed both incidents. Company statements Ministry response, reported November 13
The company has acknowledged a PG-mixture spill at an operating data center. The later pond event remains a separate question. We have the reported company and ministry statements; assessing the connection would require the spill file and full laboratory results, including when and where samples were taken.
Propylene glycol · EPA cleanup report
Fred Meyer distribution center
Clackamas, Oregon · August 2014
A contractor working on the building’s sprinkler system collected used propylene glycol in drums, then emptied about 120 US gallons into a storm drain. Some reached Carli Creek. EPA’s final report describes the cleanup and water sampling.
The incident shows how routine maintenance can send fluid into a waterway. Workers need to know where drains lead and how to collect used liquid.
One early creek sample contained 6.37 mg/L of PG. Four other samples were below the laboratory’s reporting limit of 5 mg/L. Those results leave the amount below that limit unknown. EPA reported that cleanup was complete.
Deicing runoff · Justice Department record
Detroit Metropolitan Airport
Romulus, Michigan · May 2001; guilty plea June 2006
Airport personnel opened valves that released roughly 25 million gallons of pond water into the Frank and Poet Drain. The ponds held runoff from deicing products, including ethylene glycol and propylene glycol. Investigators found the discharge while looking into a fish kill.
Collection ponds depend on working treatment connections and control over the valves that release their water. This case also shows the importance of reporting a discharge.
The 25-million-gallon figure describes pond water containing deicing material. In 2006, the Airport Authority pleaded guilty to negligently failing to report the discharge.
Propylene glycol · city updates
Glens Falls Recreation Center ice rink
Glens Falls, New York · 2025
Employees noticed the coolant level falling in January. The city identified propylene glycol in March. In October, it reported that testing found glycol in soil and groundwater beneath the building. After temporary repairs, the city said the system was holding its fluid.
Checking fluid levels can reveal a hidden leak. The city then needed to locate the contamination, check the repairs, and plan longer-term work on its aging cooling system.
The city said testing showed the contamination stayed beneath the building. The case concerns an older ice-rink system and gives a concrete example of the work required after an underground coolant leak.
City of Glens Falls (2025-03-25) · City of Glens Falls (2025-10-31)
Water leak · Google incident report
Google Cloud Paris region
Paris, France · April 25–26, 2023
Water entered Google’s space from another room above its equipment. A battery room flooded and caught fire, equipment shut down, and recovery required extensive cleaning.
A leak above electrical equipment can spread damage across a building. Google’s follow-up work included reviewing water routes and considering drip trays.
Google describes water in its report and leaves its chemical composition unspecified. The incident illustrates how liquid can damage equipment and interrupt service.
The 2014 Freedom Industries spill into West Virginia’s Elk River involved crude MCHM and polyglycol ethers, chemicals used in coal processing. The Chemical Safety Board’s investigation describes tank corrosion and failed containment. Those findings are relevant to storage design. Comparing the spill’s health effects with PG25 requires accounting for the different chemicals. CSB investigation
06 · Keeping the system working
Check the fluid, track losses, and plan for repairs.
The Open Compute Project recommends checking glycol concentration and pH every quarter and recording the results. It also discusses annual laboratory testing where needed. Results outside the supplier’s acceptable ranges can lead to adjustment or replacement of the fluid. The equipment requirements, supplier’s advice, and test results guide the replacement schedule. OCP §§5–6
Operators can track how much liquid they add and compare that with service records. An unexplained fall in fluid level calls for investigation. Repairs may require draining part of a loop, replacing a component, collecting the old liquid, and refilling the pipes. Workers need the right containers and a clear disposal route before they start.
Manufacturers build safeguards into some equipment. IBM’s 9175 system includes drip trays, low-fluid warnings, pump leak sensors, and a spill kit. A site review should identify which safeguards its equipment provides and how staff will respond to them. IBM §3.3
Delivery, initial filling, maintenance, and final removal each involve handling liquid outside normal operation. For each step, the plan should name the person responsible, explain how to stop a spill, and show where the collected fluid will go.
07 · Michigan rules
Water protection and waste rules apply to coolant handling.
Protecting waterways. Michigan law prohibits direct or indirect discharges of substances that are or may become harmful to state waters and their uses, including aquatic life. MCL 324.3109(1)
Stormwater permits. EGLE considers the facility’s activities, whether rain can reach industrial materials, and where runoff goes when deciding which industrial stormwater requirements apply. The site’s permit and drainage plan show what discharges are allowed. Construction and operating permits need to be checked for their respective requirements. EGLE guidance
Used coolant. EGLE says used antifreeze can be hazardous or non-hazardous depending on its condition and contents. Michigan offers several ways to manage it, including rules for hazardous waste, universal waste, and non-hazardous liquid industrial by-products. The operator must identify the waste and follow the handling and transport rules for the chosen route. EGLE §2.7.15
Spill plans. Federal Spill Prevention, Control, and Countermeasure rules, known as SPCC, cover oils. A data center’s diesel fuel may fall under those rules. Coolant needs its own assessment of storage, leak control, and recovery. EPA’s description of SPCC
Lessons from airports. The federal airport deicing rule applies to airport operations. Its treatment requirements grew out of experience with glycol runoff. For a data center, the applicable laws, permits, and site conditions determine the requirements. 40 CFR 449.1
08 · Questions for a proposed facility
Ask for details that can be checked.
These questions can help residents, local officials, and engineers review a proposal. Some answers come from permits; others require construction drawings, supplier documents, or operating plans.
What fluid will the facility use?
Ask for the product name, supplier, safety data sheet, additives, and glycol concentration for each loop. The supplier should explain whether the percentage is measured by weight or by volume.
How much could escape from a break?
Ask how much coolant each part of the system holds, which valves can close it off, and how quickly they close. Include tanks and pumps that could keep feeding liquid into a broken pipe.
Where would a spill go?
Trace the drains from roofs, equipment rooms, yards, and delivery areas. Ask how the site would hold spilled coolant, including during rain or firefighting, and how workers would remove it.
How will staff find a leak?
Ask about fluid-level and leak alarms, records of added coolant, automatic shutdowns, alarm testing, and who responds when an alarm sounds.
What happens during maintenance?
Ask how the fluid will be tested, when it will be replaced, how workers will collect it, and which recycler or disposal facility will receive it. Any proposed sewer disposal needs acceptance from the sewer authority.
How will effects on nearby water be checked?
Ask how groundwater flow and surface drainage affect the sampling plan. The plan should explain what will be measured, where and when samples will be taken, how small an amount the laboratory can detect, and who acts on the results.
With those answers, a community can evaluate the water savings, understand what a leak could affect, and see how the operator plans to prevent and handle one.