01 · The three tiers
The tiers share one method and differ in how strict the numbers are.
A sound limit has two parts: a number and a method. The number is a level such as 45 decibels. The method says what is measured, how long the reading is averaged, and where the microphone goes. The report found that two rules that both say “50 dBA” can differ by 10 decibels or more in practice, because they measure in different ways. So the method matters more than the number.
Some terms first. A decibel (dB) is the unit of sound level. dBA is a reading that counts sound the way the human ear hears it, so it gives less weight to low-pitched sound. dBC counts low-pitched hum more fully. Leq (equivalent continuous sound level) is the average sound energy over a stated period, such as 15 minutes. L90 is the level the sound stays above 90 percent of the time. It describes the quiet floor of a place. The ordinance calls that quiet floor background sound.
Every tier uses the same method. Daytime runs from 7 a.m. to 10 p.m., and nighttime from 10 p.m. to 7 a.m. The limits apply to the sound the data center adds, called facility sound, not to all the sound at a place. They apply at a receptor point: any point on or beyond the property line of a neighbor’s parcel, 5 feet above the ground. That neighbor may live inside or outside the township. Pittsfield Capitol Properties
The three tiers then differ in the numbers, and in how much testing and monitoring they require.
- Baseline (B)A floor for loud places, such as land next to a highway or in an industrial park. The report says Baseline is “a floor, not a goal,” because complaints arise at levels it allows.
- Recommended (R)The report’s default for a township with homes within about a mile of the site. It adds independent review, five years of yearly tests, and two years of monitoring.
- Most protective (MP)For quiet rural places where night background sound is in the low 30s and homes are close. It may rule out some sites, and a township that picks it should say so in its findings.
| Element | Baseline | Recommended | Most protective |
|---|---|---|---|
| Where it fits | Loud settings, such as by a highway or in an industrial park. | Most places with homes within about a mile. | Quiet rural places with close homes; may rule out some sites. |
| Night limit (10 p.m.–7 a.m.) | 50 dBA | 45 dBA | 40 dBA |
| Day limit (7 a.m.–10 p.m.) | 55 dBA | 50 dBA | 45 dBA |
| C-weighted limit | 70 dBC day, 65 night. A gap (dBC minus dBA) over 10 dB requires band analysis. | 65 dBC day, 60 night. Gap no more than 20 dB. | 60 dBC day, 55 night. Gap no more than 20 dB. |
| Octave-band limits | 16–8,000 Hz reported in tests; no limit. | 65 dB at 16, 31.5, and 63 Hz, at all hours. | Full table, 16–8,000 Hz, never above 65 dB (Table 1 in Section 5). |
| Tonal penalty | 5 dB, named test. | 5 dB, named test, presumed in models unless disproven; a tone-free design avoids it. | 10 dB, with the same test. |
| Background cap | None; background reported. | Night: lower of the limit or L90 + 10 dBA. | All hours: lower of the limit or ANS-weighted L90 + 5 dBA. |
| Floor | No cap or tonal penalty sets an effective limit below 35 dBA, in any tier. | ||
| Averaging period | 1-hour Leq | 15-minute Leq | 10-minute Leq |
| Modeling margin | None. | Model meets each limit by 3 dB. | As Recommended. |
| Generator testing | Weekdays 8–6; meet day limits; 100 hours per generator a year (all tiers). | Weekdays 9–5; one per building; 60-minute tests plus one 2-hour annual load test; 24 hours’ notice. | Weekdays 10–4; one on site; one 30-minute test a month plus one 2-hour annual load test (72 hours’ notice). Outages: 55 dBA. |
| Vibration | None perceptible at the property line. Construction: 0.2 in/s PPV at homes. | 0.01 in/s PPV. Construction: survey structures within 500 ft; monitor PPV. | Also 0.10 mm/s RMS; continuous monitoring through year one. |
| Background sound survey | 7 days with a weekend at 2 or more locations; one-third-octave data. | At least 3 locations. | Two 7-day surveys, one in November–March. |
| Independent review | Optional, at the applicant’s cost. | Required; township picks, applicant funds escrow. | Reviewer also witnesses tests and audits data. |
| Post-construction test | Within 90 days of each phase. | Within 60 days; yearly for 5 years at summer peak. | Yearly for life, summer and winter night. |
| Continuous monitoring | None. | One or more stations for 2 years; monthly reports. | Permanent stations each direction; public data. |
| Complaint response | Answer in 2 business days; investigate in 14 days. | Answer in 24 hours; test in 7 days at operator cost; plan in 30 days. | 24-hour line; test in 72 hours; plan in 30 days. |
| Penalties and security | Civil infraction, escalating fines; 30-day cure. | 30-day cure, then suspension; guarantee for mitigation. | 30-day cure; also curtailment orders; revocation 90 days after suspension. |
All dBA and dBC limits are Leq values for the facility’s sound, 5 feet above the ground. PPV is peak particle velocity, the top speed of a shaking surface. RMS is root mean square, a kind of average. The ANS-weighted L90 leaves out the highest-pitched sound, so that insects and rustling leaves do not make a quiet place look louder. The report marks some values as its own judgment, because no source sets them. These include the 35 dBA floor, the 10-minute averaging period, the survey location counts, the 2-year monitoring period, the complaint response times, the cure periods, the notice periods, the 500-foot survey radius, the winter test, and the hard-ground model run.
Where the main numbers come from
Most values come from a health guideline, a federal or state rule, or an adopted local code. Baseline’s 55 dBA by day matches the 1999 World Health Organization (WHO) threshold for serious annoyance outdoors and EPA’s 1974 outdoor level of 55 dB Ldn, a day-night average. Its 5 dB tonal penalty is the ANSI S12.9 Part 4 adjustment, which the Michigan Public Service Commission adopted for energy facilities over utility objection. Linn County, Iowa pairs 55 dBA with 65 dBC as hourly averages. WHO 1999 EPA 1974 MPSC order Linn County
Recommended’s 45 dBA at night equals WHO’s 1999 value outside a bedroom, set so people can sleep with windows open. It also equals WHO’s 2018 night value for road traffic, applied here by analogy, since WHO set no value for industry. New York uses 45 dBA at homes in its siting rules. The night background cap of L90 plus 10 dBA tracks the Massachusetts noise policy, which is a guideline rather than an enforceable standard. WHO 1999 WHO 2018 New York siting rule MassDEP
Most protective’s 40 dBA at night is WHO’s 2009 night guideline. Its cap of background plus 5 dBA follows Henrietta Township, Michigan and Coweta County, Georgia. Clark Township, Michigan adopted 45 dBA by day and 40 dBA at night, or ambient L90 plus 5 dBA if lower. WHO 2009 Henrietta Township Coweta County Clark Township
Baseline will not prevent complaints. Virginia’s legislative auditors found that resident complaints arose at 40 to 59 dB, “typically below the 55 or 60 decibel limit” that the large Northern Virginia counties allow. JLARC 2024
What the 35 dBA floor does
Below about 35 dBA, wind on the microphone and the meter’s own electrical noise make rural readings unreliable. Without a floor, a penalty could push a limit below that level. For example, a 10 dB tonal penalty on a 40 dBA limit would require 30 dBA. So no cap or penalty may set an effective limit below 35 dBA, in any tier.
Mixing tiers
A township may mix tiers. It might adopt Recommended limits with Most protective monitoring, or Baseline limits in an industrial park and Recommended limits elsewhere. If it mixes tiers, every limit should still use one averaging period, one measurement location, and one set of definitions. Then one meter reading can answer every question.
How to choose
The report suggests four steps. First, measure the background sound at night. Second, map the distances from likely sites to homes. Third, choose the tier and record the reasons in the findings: the measured background, the health basis, and the ordinances other places have adopted. Fourth, adopt the procedures in full. A strict number without testing, monitoring, and enforcement is weaker than a moderate number with them.
02 · Can a design meet it?
Recommended is demanding. A design must model at about 42 dBA at night, or 37 with a tone.
The limit on paper is not the design target. Two rules push the target lower.
- The modeling margin. Recommended and Most protective require the sound study to show that the design meets each limit by at least 3 dB. That is the accuracy of plus or minus 3 dB usually quoted for ISO 9613-2, the standard computer model for outdoor sound. Piercy 1993
- The tonal penalty. If the sound has a prominent tone, such as a steady hum from a transformer or fan, the ordinance adds 5 dB (or 10 dB in Most protective) to the reading before comparing it with the limit.
These targets are stated in Section 9 of the report. Baseline has no modeling margin, so its design target is the limit itself. In Most protective, a facility with a prominent tone faces the 35 dBA floor at night, so in practice the design must have no prominent tone.
Few studies meet the Recommended target. The report reviewed applicant sound studies for data centers. Models reach about 45 dBA at homes with ordinary measures, and 40 dBA is at the edge. Only Coal City, Illinois, at a maximum of 41 dBA at night, models at or below 42. Chantilly Premier, Virginia (40 to 42 dBA) does too, but its study reports daytime levels only. The T5 study in Chantilly (45 dBA) and the Smithfield, Pennsylvania study (38 to 47 dBA) would not pass as modeled. Coal City study Chantilly Premier study T5 study Smithfield study
The same margin puts the Recommended night dBC target at 57 dBC. The T5 design meets that exactly. The Raylan, Kentucky design misses it by 10. Raylan study
So the Recommended tier will push designs toward more distance from homes, control of tones at the source, and fewer outdoor fans. The tier rewards a design with no prominent tone. If the study’s tone check, based on one-third-octave data, shows no prominent tone, and the test after construction confirms it, the design models against 42 dBA instead of 37. A township that finds 42 dBA too hard for its sites can lower the margin, since the model brackets it. The cost is that more of the risk of a wrong model falls on the neighbors and on the test after construction.
The Most protective tier is at or beyond the edge of what designs have shown. No applicant study the report reviewed predicts even 40 dBA at every home at night. A large air-cooled campus would probably need a setback on the order of a mile plus the full set of source treatments. Distance alone is not enough: the Raylan design, 3,200 to 5,700 feet from homes, still models 45 to 49 dBA. Raylan study
The caveat: these are predictions
Every applicant study is a prediction made before construction. The report found no published measured test in the United States showing a large operating data center at 45 dBA or less at homes. The one measured retrofit series, at Tanner Way in Prince William County, Virginia, reached 48 to 55 dBA by residents’ readings, short of the 45 dBA they sought. The closest measured case is abroad: a 2025 verification report for a Microsoft data center near Sydney, Australia calculated about 30 and 32 dBA at two receivers, because the facility was too quiet to measure there directly. A 2026 review found that “calibrated, standards-grade acoustic data remain scarce.” This is why the ordinance requires a test after construction. Sydney verification report Bray and Dominici
03 · Ordinance text
Pick a tier to fill in its numbers.
How to use this text (from Appendix B)
- Choose a tier for each bracket. Brackets show the three tiers as [B: … / R: … / MP: …], for Baseline, Recommended, and Most protective. Pick one value and delete the others. For example, a township choosing the Recommended tier turns “during nighttime, [B: 50 / R: 45 / MP: 40] dBA” into “during nighttime, 45 dBA.” Tiers may be mixed, but every limit must use the same averaging period, location, and procedure.
- Fill the other blanks. Items such as [Township], [Zoning Administrator], and dollar amounts depend on local law and practice.
- Fit it to the state enabling law. Decide whether each part belongs in the zoning ordinance, the general police-power ordinance, or both. In Michigan, the planning commission drafts zoning text and the township board adopts it; the board alone adopts the general ordinance. Check state preemption first.
- Confirm standards and editions. Standards are revised. Confirm the current edition of each named standard before adoption, and decide whether the ordinance names a fixed edition or “the current edition.”
- Have the local attorney review it. This text is a starting point for drafting. It is not legal advice and has not been reviewed for any particular jurisdiction.
The text uses “Township” throughout. Substitute “City,” “Village,” or “County” as needed. Drafting notes, set in italics, explain choices and are not part of the ordinance.
Showing all three tiers. Each bracket lists the Baseline (B), Recommended (R), and Most protective (MP) values.
Model Data Center Noise and Vibration Ordinance
Section 1. Purpose and findings
- (a)Purpose. This ordinance protects the public health, safety, and welfare of Township residents from noise and vibration produced by data centers and their accessory equipment. It sets measurable limits, requires studies before and after construction, and provides a procedure for enforcement.
- (b)Findings. The [Township Board] finds that:
- (1)Data centers operate cooling, electrical, and standby power equipment that runs day and night and can produce steady, tonal, and low-frequency sound audible at nearby homes.
- (2)Sleep disturbance and annoyance from environmental noise are well documented, and both are greater at night, for tonal and low-frequency sound, and in quiet places.
- (3)A-weighted sound limits alone do not adequately control low-frequency and tonal sound.
- (4)The measured nighttime background sound in the Township is [insert measured range and source].
- (5)Design choices made before construction, such as siting, equipment selection, and enclosures, control noise more effectively and at lower cost than repairs after construction.
- (6)Measured limits with a stated method give operators a clear design target and give the Township an enforceable standard.
- (7)[Most protective tier, Michigan:] A data center that meets this ordinance can be located at [describe the districts or areas where a compliant facility could locate].
- (1)
Drafting note. Findings (1) through (3) and (5) rest on the report’s Sections 3 and 4. Finding (4) should cite the Township’s own survey. Finding (7) answers MCL 125.3207, which bars zoning that has “the effect of totally prohibiting” a use where there is demonstrated need MCL 125.3207. A tier choice is easier to defend when the findings explain it.
Section 2. Definitions
In this ordinance, the following words have these meanings.
- (a)A-weighted sound level (dBA) means the sound level measured with the A frequency weighting defined in IEC 61672-1.
- (b)Accessory equipment means any equipment on the site that serves the data center, including chillers, cooling towers, dry coolers, fans, air handlers, pumps, transformers, substations, battery storage, generators, load banks, and on-site power generation.
- (c)Background sound means the A-weighted L90 of all sound at a place when the facility is not operating, measured under ANSI/ASA S12.100 and Section 8. For a data center in operation on the effective date, background sound is found under Section 4(c)(3). [MP: Background sound is the ANS-weighted L90: the A-weighted level with the octave bands above 1,000 Hz removed, so that insects and rustling leaves do not count.]
- (d)C-weighted sound level (dBC) means the sound level measured with the C frequency weighting defined in IEC 61672-1. It counts low-frequency sound more fully than dBA.
- (e)Data center means a facility whose primary use is to house computer servers and related equipment that store, process, or transmit data, together with its accessory equipment. The term includes cryptocurrency mining facilities. [Optional threshold: The term applies only to facilities with a design electrical demand of [ ] megawatts or more.]
- (f)Daytime means 7 a.m. to 10 p.m. Nighttime means 10 p.m. to 7 a.m.
- (g)Emergency operation has the meaning in Section 7(a).
- (h)Equivalent continuous sound level (Leq) means the steady sound level that contains the same sound energy as the actual varying sound over a stated period. “Leq(15 min)” means an Leq over 15 minutes.
- (i)Facility sound means the sound produced by the data center and its accessory equipment, separate from all other sound.
- (j)L10, L50, and L90 mean the levels exceeded 10, 50, and 90 percent of the time during a measurement period. The L90 is the quiet level that the sound stays above for 90 percent of the period.
- (k)Load bank means a device that places an artificial electrical load on a generator for testing, including its cooling fans.
- (l)Nonparticipating property means any parcel except (1) a parcel owned or leased by the operator, or (2) a parcel covered by a waiver agreement. A waiver agreement is a written agreement between the owner and the operator, recorded with the [register of deeds], that expressly waives the sound limits of this ordinance for that parcel. An easement or agreement for any other purpose, such as a utility line, access, or drainage, is not a waiver agreement. [Optional: The Township does not recognize waiver agreements; delete clause (2) and the two sentences after it.]
- (m)Octave band means a band of frequencies whose upper limit is twice its lower limit, named by its center frequency (16, 31.5, 63, 125, 250, 500, 1,000, 2,000, 4,000, or 8,000 Hz). A one-third-octave band is one third of an octave band. An octave-band level is the unweighted Leq in an octave band, in decibels (dB).
- (n)Operator means the owner, lessee, and any person who operates the data center, each of whom is responsible for compliance.
- (o)Peak particle velocity (PPV) means the maximum instantaneous speed of a vibrating surface, in inches per second.
- (p)Phase means a building, or a group of outdoor equipment, that the approved site plan shows being placed into operation at one time.
- (q)Prominent tone means a tone identified under Section 5(c).
- (r)Qualified acoustical consultant means a person who is board certified by the Institute of Noise Control Engineering, or a licensed professional engineer with at least [five] years of experience in environmental acoustics. The person may have no financial interest in the project other than the fee for the work.
- (s)Receptor point means any point on or beyond the property line of a nonparticipating property, 5 feet (1.5 meters) above grade. A receptor point may be inside or outside the Township. [B: Receptor points are limited to nonparticipating property zoned or used for residences.]
- (t)Residual sound means the sound at a place at the time of a measurement when the facility is not operating, or when the equipment being tested is shut down.
- (u)Reviewer means the qualified acoustical consultant the Township retains under Section 10. If the Township does not retain a reviewer, references to the reviewer mean the Township.
- (v)RMS particle velocity means the root-mean-square speed of a vibrating surface over a 1-second period, in millimeters per second. A value of 0.10 mm/s is about 0.004 inch per second.
- (w)Site means the parcel or parcels on which the data center and its accessory equipment are located.
- (x)Sound level meter means an instrument that meets the Class 1 requirements of IEC 61672-1:2013 (ANSI/ASA S1.4-2014 Part 1), with one-third-octave band capability.
- (y)Studies and tests. The background sound survey is the survey required by Section 8. The predictive study is the study required by Section 9. A compliance test is a test under Section 11.
- (z)Vibration means oscillating motion of the ground or a structure.
Drafting note. The night period matches the day-night level (Ldn) and Pittsfield Charter Township, Michigan FTA manual Pittsfield. The receptor definition reaches any nonparticipating parcel whatever its zoning, which avoids the gap in Capitol Properties Capitol Properties. Wixom, Michigan measures “at or beyond the nearest receiving property line,” including in neighboring communities Wixom. The definition of nonparticipating property turns on an express waiver of the sound limits, so a neighbor who grants an ordinary utility or access easement keeps full protection.
Section 3. Applicability
- (a)This ordinance applies to every new data center, to every expansion or modification under Section 15, and to every data center operating under an approval granted after the effective date.
- (b)[General ordinance version only:] The following also apply to data centers in operation on the effective date: Sections 1 and 2; Section 4, except subsection (g); Section 5, except the predictive-study sentences of subsection (d); Section 6(a) and (b); Section 7; Section 9(f); Section 11, except subsection (e); Sections 13 and 14; Section 16, except subsection (e); Section 17; and [R and MP: Sections 10 and 12]. An existing data center shall complete a compliance test under Section 11 within [180] days of the effective date. Background sound for an existing data center is found under Section 4(c)(3).
- (c)This ordinance applies in addition to the Township’s general noise ordinance. Where they differ, the stricter provision applies.
- (d)Construction activity is governed by Section 6(c) and by the Township’s general construction noise rules.
- (e)[Michigan:] This ordinance does not apply to an energy facility to the extent that 2023 PA 233 governs it.
Drafting note. In Michigan, zoning standards generally do not reach lawful existing uses, but a general ordinance can MCL 125.3208 Natural Aggregates. Subsection (b) belongs only in the general ordinance version. An existing data center never had a background sound survey, so subsection (b) relies on shutdown tests instead.
Section 4. Sound limits
- (a)A-weighted limits. Facility sound at any receptor point shall not exceed:
- (1)during daytime, [B: 55 / R: 50 / MP: 45] dBA; and
- (2)during nighttime, [B: 50 / R: 45 / MP: 40] dBA.
- (1)
- (b)Averaging period. Each sound limit in Sections 4, 5, and 7 is an Leq over [B: 1 hour / R: 15 minutes / MP: 10 minutes]. Each period begins on the hour or at a whole multiple of its length after the hour. For example, 15-minute periods begin at :00, :15, :30, and :45. Each period in which facility sound exceeds a limit is a separate exceedance.
- (c)Background cap. [B: Delete this subsection.]
- (1)[R: During nighttime / MP: At all times], facility sound at a receptor point shall also not exceed the background sound at that point plus [R: 10 / MP: 5] dBA. Where this cap is lower than the limit in subsection (a), the cap applies.
- (2)Background sound at a receptor point is the median of the hourly L90 values for the same period (daytime or nighttime) over the whole background sound survey. It is taken at the survey location nearest the receptor point in the same direction from the site, as stated in the survey report under Section 8(g).
- (3)For a data center in operation on the effective date, background sound is the median L90 measured during 1-hour shutdown tests under Section 9(f)(6) on at least [three] different days or nights. Instead, the reviewer may approve a 7-day measurement under Section 8 at a comparable location away from the facility.
- (1)
- (d)Floor. No cap under subsection (c) shall be set below 35 dBA. Facility sound that carries a tonal penalty under Section 5(d) complies with this section if its level, before the penalty, does not exceed 35 dBA.
- (e)Low-frequency and tonal limits. Facility sound shall also meet Section 5.
- (f)Facility sound, not total sound. The limits apply to facility sound. Where other sound is present, facility sound is found under Section 9(f).
- (g)Modeling margin. A facility shall not be approved unless the predictive study shows that facility sound will meet each limit by at least [B: 0 / R: 3 / MP: 3] dB at every receptor point.
Drafting note. The numbers and their sources are in the report’s Section 9. The 3 dB margin reflects the plus or minus 3 dB accuracy usually quoted for ISO 9613-2 Piercy 1993. With that margin, a Recommended design must model at about 42 dBA at night, or 37 dBA if the tonal penalty applies (report Section 9). A township may lower the margin, at the cost of leaving more of the risk of a wrong model with the neighbors. The 35 dBA floor in subsection (d) keeps every effective limit at a level that can be measured reliably at a rural site.
Section 5. Low-frequency and tonal provisions
- (a)C-weighted limits. Facility sound at any receptor point shall not exceed [B: 70 / R: 65 / MP: 60] dBC during daytime or [B: 65 / R: 60 / MP: 55] dBC during nighttime. [R and MP:] The C-weighted level of facility sound shall not exceed its A-weighted level by more than 20 dB. [B:] If the C-weighted level exceeds the A-weighted level by more than 10 dB, the predictive study or compliance test shall identify the octave bands and sources responsible and the mitigation considered.
- (b)Octave bands.
- (1)Every compliance test shall report facility sound in each octave band from 16 to 8,000 Hz. Every predictive study shall report the octave bands it models under Section 9(b).
- (2)[R and MP:] In addition, facility sound at any receptor point shall not exceed an octave-band level of 65 dB in any of the 16, 31.5, or 63 Hz octave bands.
- (3)[MP:] In addition to paragraph (2), facility sound at any receptor point shall not exceed the octave-band levels in Table 1.
- (1)
- (c)Prominent tones. A prominent tone is present when the Leq in a one-third-octave band exceeds the Leq in both adjacent bands by at least a set margin. The margin is 15 dB for bands from 25 to 125 Hz, 8 dB from 160 to 400 Hz, and 5 dB from 500 to 10,000 Hz. The test follows ANSI/ASA S12.9 Part 4, Annex C, or ISO 1996-2, Annex K. [R and MP: For tones from 50 Hz upward, the applicant may instead show under ISO/TS 20065 that the tone is not audible at the receptor point.]
- (d)Tonal penalty. When facility sound contains a prominent tone at a receptor point, [B: 5 / R: 5 / MP: 10] dB shall be added to its measured or modeled A-weighted level before it is compared with Section 4. The qualified acoustical consultant preparing the study or test shall make this adjustment. The floor in Section 4(d) applies. [R and MP: That consultant shall apply the penalty in the predictive study unless the study’s tonal assessment, based on one-third-octave source data, shows no prominent tone at any receptor point. Where the study does not apply the penalty, the initial compliance test shall include a tonal assessment at each receptor point.]
- (e)[MP:] Indoor low-frequency test. On a complaint about low-frequency sound, and with the occupant’s written consent, the Township may require a one-third-octave measurement inside the complainant’s home, with windows closed, under ANSI/ASA S12.9 Part 7. The results shall be reported to the Township and the occupant and used to design any corrective action.
| Octave band center (Hz) | 16 | 31.5 | 63 | 125 | 250 | 500 | 1,000 | 2,000 | 4,000 | 8,000 |
|---|---|---|---|---|---|---|---|---|---|---|
| Daytime | 65 | 65a | 65a | 65 | 57 | 51 | 45 | 39 | 34 | 32 |
| Nighttime | 65 | 63 | 61 | 55 | 47 | 40 | 35 | 30 | 25 | 25 |
Source: 31.5–8,000 Hz: Illinois Pollution Control Board limits for sound from Class B (commercial) sources received on Class A (residential) land, 35 Ill. Adm. Code 901.102 Illinois Part 901. 16 Hz, and the daytime cap at 31.5 and 63 Hz: ANSI S12.9 Part 4 level below which low-frequency annoyance is generally minimal ANSI S12.9 Part 4.
(a) Illinois allows 72 dB at 31.5 Hz and 71 dB at 63 Hz by day. These are capped at 65 dB, the Recommended tier’s band limit, so the Most protective tier is never looser than the Recommended tier. Illinois measures at any point within the receiving land at least 25 feet from the noise source; this table applies at receptor points. Illinois daytime is 7 a.m. to 10 p.m., the same as Section 2(f).
Drafting note. The tone test margins are the ANSI S12.9 Part 4 and ISO 1996-2 values that Stafford County, Virginia adopted ANSI S12.9 Part 4 ISO 1996-2 Annex K summary Stafford County. ISO/TS 20065 is not validated below 50 Hz ISO/TS 20065. The 20 dB gap cap follows Hessler Hessler 2004 and Pittsfield Pittsfield. A design that removes prominent tones avoids the penalty, which is the main route to the Recommended and Most protective tiers. Do not adopt an octave-band clause without numbers MTA sample Gasper.
Section 6. Vibration
- (a)Operating limit. Vibration from the facility, measured at or beyond the property line of any nonparticipating property [R and MP: under ANSI/ASA S2.71 or ISO 2631-2], [B: shall not be perceptible to a person without instruments / R: shall not exceed a peak particle velocity of 0.01 inch per second in any direction / MP: shall not exceed a peak particle velocity of 0.01 inch per second, nor an RMS particle velocity of 0.10 millimeter per second, in any direction].
- (b)Equipment isolation. The operator shall mount generators, chillers, pumps, fans, and transformers on vibration isolators designed to meet subsection (a).
- (c)Construction. During construction:
- (1)vibration at any residential structure shall not exceed a peak particle velocity of 0.2 inch per second, or 0.12 inch per second at a structure that a condition survey identifies as fragile or historic;
- (2)[R and MP:] before pile driving, blasting, or other high-vibration work, the operator shall offer a photographic condition survey to the owner of every structure within [500] feet. During that work, the operator shall monitor peak particle velocity at the nearest structures and stop work when a limit is reached;
- (3)[MP:] the operator shall monitor vibration continuously at the property lines nearest homes during construction and the first year of operation; and
- (4)high-vibration work shall occur only from [8 a.m. to 6 p.m.] on weekdays.
- (1)
Drafting note. The 0.2 and 0.12 in/s construction values are FTA damage criteria FTA manual. People barely perceive continuous vibration at about 0.01 in/s PPV Caltrans 2020. Saginaw Charter Township uses 0.01 in/s PPV, and Pittsfield uses 0.10 mm/s RMS under ANSI S2.71 Saginaw Charter Township Pittsfield. Operating vibration is rarely felt off site; the limits mainly guard against poor isolation Smithfield study.
Section 7. Emergency and backup generators
- (a)Emergency operation means operation of a generator during an interruption of utility power to the site, or during an emergency declared by the electric utility or regional grid operator. Operation for economic reasons, demand response, peak shaving, or routine power supply is not emergency operation.
- (b)Continuous on-site generation. Any turbine, engine, or other generator that supplies power other than in emergency operation or testing is accessory equipment subject to Sections 4 through 6 at all times.
- (c)Testing. Generator testing, maintenance runs, and load bank operation:
- (1)shall occur only on weekdays, not on federal or state holidays, between [B: 8 a.m. and 6 p.m. / R: 9 a.m. and 5 p.m. / MP: 10 a.m. and 4 p.m.];
- (2)shall meet the daytime limits of Sections 4 and 5, including the sound of any load bank;
- (3)[R:] shall run only one generator per building at a time, for no more than 60 minutes per test; [MP:] shall run only one generator on the site at a time, with no more than one routine test per generator per month, each of no more than 30 minutes;
- (4)[R and MP:] may also include, for each generator, one annual full-load test of no more than [2] hours, which may use a load bank and is otherwise subject to this subsection;
- (5)shall not exceed 100 hours per generator per calendar year [Optional: and [100] hours per year for all generators on the site combined]; and
- (6)[R:] shall be posted on a public website at least 24 hours in advance. [MP:] shall be posted on a public website at least 24 hours in advance for routine tests and at least 72 hours in advance for each annual full-load test.
- (1)
- (d)Emergency operation limit. [B and R:] Emergency operation is exempt from Sections 4 and 5. [MP:] During emergency operation, facility sound at any receptor point shall not exceed 55 dBA.
- (e)Records. The operator shall log the date, start and end time, generator, load, and reason for every generator operation, and shall give the log to the Township [monthly / on request]. The operator shall report each emergency operation lasting more than one hour to the Township within 5 business days.
Drafting note. The 100-hour limit matches the federal cap on maintenance and testing of emergency engines 40 CFR 60.4211(f)(2). Pittsfield Charter Township, Michigan caps testing at 100 hours a year for the whole site, which the optional clause in (c)(5) adopts Pittsfield. The 30-minute monthly test follows CyrusOne’s posted schedule in Aurora, Illinois, and the 10 a.m. to 4 p.m. window follows Henrico County, Virginia CyrusOne Henrico County. The 2-hour annual test matches Fairfax County, Virginia’s daily testing allowance Fairfax County. Lower Saucon Township, Pennsylvania applies 55 dBA during outages Lower Saucon Township. Load banks can be louder than the generator they serve Chantilly study.
Section 8. Pre-application background sound survey
- (a)When. Before applying, the applicant shall complete a background sound survey. The Township shall approve the survey plan, including locations and dates, before it begins.
- (b)Who. A qualified acoustical consultant shall conduct the survey. [R and MP: The reviewer may observe it.]
- (c)Locations. Measurements shall be made at [B: two / R: three / MP: three] or more locations representing the nearest nonparticipating properties in each direction with homes.
- (d)Duration. Unattended monitoring shall run for at least 7 consecutive days, including every night and at least one weekend. [MP: Two such surveys shall be made, in different seasons, one of them between November and March.]
- (e)Data. The survey shall store the A-weighted and C-weighted Leq for each 1-second period, and one-third-octave band Leq from 12.5 to 10,000 Hz for each 1-minute period. From the stored data, it shall report the Leq, L10, L50, and L90 in dBA and dBC for each 10-minute and each 1-hour period [MP: and the ANS-weighted L90 for each hour]. It shall log wind speed and direction at microphone height, temperature, and precipitation, and shall record audio samples sufficient to identify sources.
- (f)Methods. The survey shall use sound level meters as defined in Section 2, calibrated before and after each deployment. It shall follow the applicable parts of ANSI/ASA S12.9, ANSI/ASA S12.18, and ANSI/ASA S12.100. Periods with wind above the limits of Section 9(f)(3), precipitation, or unrelated events shall be excluded and listed.
- (g)Report. The report shall give, for each location, the median of the hourly L90 values for daytime and for nighttime, which is the background sound used in Section 4(c). It shall also give the lowest hourly nighttime L90 and the spectrum. The Township shall make the report public.
Drafting note. Chandler, Arizona requires a third-party baseline study before an application, and Aurora, Illinois requires a week-long study Chandler Aurora. ANSI/ASA S12.100 keeps insect and leaf sound from inflating a rural background ANSI/ASA S12.100. Storing 1-second and 1-minute data lets the same record produce the 10-minute, 15-minute, and 1-hour values that each tier uses. The median of hourly values is less sensitive to one unusual night than an average or a minimum.
Section 9. Predictive acoustic study and measurement procedure
- (a)Study required. The application shall include a predictive study prepared and sealed or signed by a qualified acoustical consultant. A data center shall not be approved unless the study shows compliance with Sections 4 through 7.
- (b)Model. The study shall use ISO 9613-2:2024, or a method the reviewer finds equivalent, with:
- (1)octave-band sound power data for each source from 63 to 8,000 Hz, and at 16 and 31.5 Hz where manufacturer data exist, taken from manufacturer test data for the specific models proposed;
- (2)all equipment running at full load, with fans at the highest speed allowed by the operating plan;
- (3)meteorological conditions favorable to sound propagation toward every receptor point;
- (4)a stated ground factor and a stated treatment of buildings, barriers, terrain, and reflections; and
- (5)[R and MP:] a stated method for the 16 and 31.5 Hz octave bands, which ISO 9613-2 does not cover, such as geometric spreading with no ground or air absorption credit. Where manufacturer data at those bands do not exist, the study shall state the source values it assumes and their basis.
- (1)
- (c)Operating cases. [R and MP:] The study shall model at least: normal nighttime operation; peak cooling on the hottest expected day; one generator test with its load bank; and emergency operation of all generators.
- (d)Results. The study shall report, at each receptor point and as contour maps, the predicted dBA, dBC, and octave-band levels. It shall include a tonal assessment under Section 5(c), using one-third-octave source data where available. It shall state the expected accuracy of the predictions. [MP: It shall include a sensitivity run with hard ground (ground factor 0) and a contour map out to 30 dBA.] It shall list each mitigation measure the applicant commits to, with the sound level each must achieve.
- (e)Files. [R and MP:] The applicant shall give the Township the model input and output files, source data, and all assumptions.
- (f)Measurement procedure. Every measurement under this ordinance shall meet these conditions:
- (1)a sound level meter as defined in Section 2, with a windscreen, calibrated in the field before and after each measurement, and laboratory-calibrated within the past [12] months;
- (2)microphone 5 feet (1.5 meters) above grade at the receptor point, at least [10 feet] from any reflecting surface other than the ground;
- (3)no precipitation, and average wind speed at the microphone no more than 5 meters per second (about 11 mph), or no more than 2 meters per second (about 5 mph) for dBC and octave-band measurements below 125 Hz;
- (4)a record of the facility’s operating state during the measurement, certified by the operator, including load, the number of chillers, fans, and generators running, fan speeds, and outdoor temperature;
- (5)facility sound is found by comparing the measured level with the residual sound (the level with the facility, or the equipment being tested, shut down). If the measured level is 10 dB or more above the residual sound, the measured level is facility sound. If it is 3 to 10 dB above, facility sound is the measured level minus the residual sound on an energy basis: Lfacility = 10 log10(10Lm/10 − 10Lr/10), where Lm is the measured level and Lr the residual sound. If it is less than 3 dB above, subtraction is not reliable. Facility sound shall then be found by a shutdown test, by measurements near the source scaled to the receptor point, or by band analysis at the tone frequencies; and
- (6)the operator shall cooperate with shutdown tests of up to [30] minutes on reasonable notice, or up to 1 hour when needed to measure background sound under Section 4(c)(3).
- (1)
Drafting note. ISO 9613-2 covers 63 to 8,000 Hz and predicts conditions that favor propagation, such as clear, calm nights ISO 9613-2:2024. FERC requires model input files from compressor applicants 18 CFR 380.12(k). The 3 dB subtraction rule follows the ANSI practice cited by Prince William County’s consultant Nelson Acoustics. The wind limits come from Caltrans Caltrans 2013 and ANSI/ASA S12.9 Part 7 ANSI S12.9 Part 7.
Section 10. Independent review paid by the applicant
- (a)Reviewer. [B: The Township may / R and MP: The Township shall] retain a qualified acoustical consultant of its choice to review the background sound survey, the predictive study, and every compliance test. [R and MP: The reviewer shall also review the monitoring station locations and reports under Section 12.] The reviewer shall have no relationship with the applicant.
- (b)Escrow. Before review begins, the applicant shall deposit [$ amount] in an escrow account held by the Township to pay the reviewer. The applicant shall replenish the account when it falls below [$ amount]. Unused funds shall be returned after the final compliance test is accepted.
- (c)Scope. The reviewer may require additional data, model runs, or measurements. [MP: The reviewer shall witness each compliance test and shall audit monitoring data under Section 12 at least once a year.]
- (d)Report. The reviewer’s report shall be public and shall be part of the record of the approval.
Drafting note. Oglethorpe County, Georgia funds county review through escrow; Wixom, Michigan requires independent peer review Oglethorpe County Wixom. The attorney should confirm the Township’s authority to require a review escrow under state law. In Michigan, the performance guarantee statute covers the cost of improvements, not review, so it does not by itself authorize this escrow (Section 16(e)).
Section 11. Post-construction compliance testing
- (a)Initial test. Within [B: 90 / R: 60 / MP: 60] days after each phase begins operation, the operator shall have a qualified acoustical consultant measure facility sound at the receptor points used in the predictive study, under Section 9(f). The test shall include daytime and nighttime measurements and one generator test.
- (b)Periodic tests. [R:] The operator shall repeat the test every year for 5 years after the last phase begins operation, between June 1 and August 31 during weekday peak cooling. [MP:] The operator shall repeat the test every year for the life of the use, with one summer peak-cooling test and one winter nighttime test each year.
- (c)Report. Each test report shall compare the results with the limits and with the predictions of the study, and shall state the operating conditions. The operator shall file it with the Township within 30 days. The Township shall make it public.
- (d)Failure. If a test shows an exceedance, the operator shall file a corrective action plan within 30 days and complete it within the period in Section 16(b). A new test shall follow completion.
- (e)[R and MP:] Certificate. A final certificate of occupancy for a phase shall not issue until its initial test shows compliance.
Drafting note. Stafford County, Virginia tests within 90 days and then yearly for 10 years at summer peak cooling. Henry County, Virginia tests yearly for the life of the use, and White County, Indiana within 60 days of each phase Stafford County Henry County White County.
Section 12. Continuous monitoring and reporting
[B: Delete this section.]
- (a)Stations. The operator shall install and maintain [R: at least one permanent sound monitoring station / MP: at least one permanent sound monitoring station in each direction with homes], at locations the Township approves, for [R: the first 2 years of operation of each phase / MP: the life of the use].
- (b)Equipment. Each station shall use a sound level meter as defined in Section 2. It shall log the A-weighted Leq for each 1-second period; the Leq in dBA and dBC and one-third-octave band levels for each 1-minute period; and the L90 for each hour. It shall record audio when levels exceed a threshold the Township sets, and shall log wind speed and precipitation.
- (c)Operating log. The operator shall keep a log of equipment operating state that can be matched to the monitoring data.
- (d)Reports. The operator shall file a monthly report summarizing the data, noting every period above a limit, and explaining its cause. [MP: The operator shall post the data on a public website within 24 hours.]
- (e)Use of data. Monitoring data may be used as evidence of a violation, subject to Section 9(f).
Drafting note. One-minute values combine exactly into the 10-minute, 15-minute, and 1-hour periods of Section 4(b). Pittsfield Charter Township, Michigan requires a public dashboard; Berkley, Michigan requires continuous vibration monitors Pittsfield Berkley. Monitor prices are quoted on request (report Section 4).
Section 13. Complaint response
- (a)Contact. The operator shall maintain a [B and R: telephone and email contact / MP: 24-hour telephone line] for noise and vibration complaints, posted at the site entrance and on a public website.
- (b)Response. The operator shall acknowledge each complaint within [B: 2 business days / R and MP: 24 hours], and shall log every complaint and its resolution. The operator shall file the log with the Township [monthly].
- (c)Testing. [B: The operator shall investigate within 14 days.] [R and MP: Within [R: 7 days / MP: 72 hours] of a complaint that gives the date, time, location, and character of the sound, a qualified acoustical consultant shall measure facility sound at the complainant’s property, at the operator’s cost. The test shall use the conditions most likely to produce the complained-of sound.]
- (d)[R and MP:] Corrective plan. If a test under subsection (c) shows an exceedance, Section 11(d) applies.
- (e)Retest trigger. If the Township receives [10] or more complaints from [3] or more households within 6 months, the operator shall conduct a full compliance test under Section 11.
- (f)Complaints are not proof. A complaint alone does not establish a violation. A violation is established only by measurement under this ordinance.
Drafting note. Augusta-Richmond County, Georgia retests after 10 complaints in 6 months Augusta-Richmond County. Subsection (f) follows Crockett, which struck a rule treating complaints as evidence of a violation Crockett.
Section 14. Records and access
- (a)The operator shall keep all studies, test reports, monitoring data, and logs required by this ordinance for at least [5] years and shall make them available to the Township on request.
- (b)The Township’s inspectors and reviewer may enter the site at reasonable times, on reasonable notice, to observe equipment and operating conditions for measurements under this ordinance.
- (c)A measurement at a receptor point on private land requires the owner’s consent. Without consent, the measurement may be made at the nearest accessible point on public land or at the property line of the site, and adjusted to the receptor point by a method the reviewer approves.
Section 15. Expansion and modification
- (a)When this applies. This section applies to any new building or phase, any added outdoor equipment, any replacement of outdoor equipment with equipment of higher sound power, and any change to the generator testing program.
- (b)Study. Before the change, the operator shall file an updated predictive study under Section 9 showing that the whole facility, including the change, will meet this ordinance. [R and MP: The change is subject to Sections 10 and 11.]
- (c)[MP:] Campus sound budget. The limits in Sections 4 through 6 apply to the combined sound of all data centers and accessory equipment on the site and on any adjacent parcel under common ownership or control. A later phase may not rely on sound headroom that an earlier phase needs to comply.
Drafting note. Two facilities that each meet a limit can together exceed it by 3 dB at a home between them FTA manual. Prince William County staff said the county could not use cumulative noise to reject a project Prince William County notes. A campus budget closes that gap for one operator.
Section 16. Enforcement and penalties
- (a)Violations. A violation of this ordinance, or of a condition of approval under it, is a [municipal civil infraction]. Each day a violation continues is a separate violation. [Michigan zoning version: A violation is also a nuisance per se.]
- (b)Notice and cure. The [Zoning Administrator] shall give written notice of a violation found by measurement. The operator shall stop or correct the violation within [30] days. For a corrective action plan that requires new equipment, the Township may approve a longer period in writing, not to exceed [180] days.
- (c)Fines. Fines shall be [$ first] for a first violation, [$ second] for a second violation within 12 months, and [$ third] for each later violation within 12 months. Fines do not accrue during a cure period under subsection (b) while the operator meets the schedule of its corrective action plan.
- (d)Suspension and revocation. [R and MP:] If a violation is not cured within the cure period, the Township may suspend the [special land use / conditional use / special exception] approval for the noncompliant phase after notice and hearing. [MP: The Township may instead order the operator to reduce the load of, or stop, named equipment until compliance is shown. It may revoke the approval for a violation not cured within [90] days after suspension.]
- (e)[R and MP:] Financial guarantee. Before a building permit issues, the operator shall provide a performance bond, letter of credit, or cash deposit. Its amount shall equal the estimated cost of the mitigation measures listed in the predictive study. The Township may draw on it to complete mitigation measures the operator fails to complete.
- (f)Costs. When a test confirms a violation, the operator shall pay the Township’s costs of the investigation and of the reviewer.
- (g)Other remedies. These remedies are in addition to any other remedy at law or in equity, including an action to abate a nuisance.
Drafting note. Michigan townships may designate violations as municipal civil infractions, and a zoning violation is a nuisance per se MCL 41.183 MCL 42.21 MCL 125.3407. Morton County, North Dakota suspends approval automatically and revokes it after 60 uncured days; Frederick County, Maryland allows 180 days to fix a measured problem Morton County Frederick County. In Michigan, MCL 125.3505 authorizes a guarantee covering “the estimated cost of improvements” to “insure faithful completion of the improvements.” It is deposited when the permit issues, and cash is rebated as work is completed MCL 125.3505. Barriers, enclosures, and silencers fit that grant. Testing and monitoring costs fit it less clearly, so subsection (e) covers mitigation only. The attorney should confirm the authority for any review or testing escrow under Section 10, and for conditions of approval under MCL 125.3504 MCL 125.3504. Fine amounts depend on state law.
Section 17. Severability
If any section, subsection, sentence, or number in this ordinance is held invalid, the holding shall not affect the rest of the ordinance. The [Township Board] declares that it would have adopted each remaining part without the invalid part.
Section 18. Effective date
This ordinance takes effect [on the date provided by state law after publication / on (date)]. It applies to any application not finally approved before that date. [General ordinance version: Section 3(b) applies to existing data centers on (date).]
Drafting note. In Michigan, a zoning amendment takes effect seven days after notice of adoption is published, unless a later date is set MCL 125.3401. In a general law township, a general ordinance with a penalty takes effect 30 days after first publication MCL 41.184. In a charter township, it takes effect on publication unless a later date is stated MCL 42.22. Whether a pending application is subject to the new rules depends on state vested-rights law.
Source: Bommarito Consulting, Noise and Vibration Rules for Data Centers (November 24, 2026), Appendix B. Model text, not legal advice.
04 · Michigan drafting notes
Notes for a Michigan township attorney.
The ordinance is written for any state, but Appendix B and Section 7 of the report flag several Michigan points. MZEA means the Michigan Zoning Enabling Act. MCL means Michigan Compiled Laws, the official code. PA means public act.
-
Two tools, two adopting bodies.
Zoning comes from the MZEA, 2006 PA 110. The planning commission drafts zoning text and holds the hearing, and the township board adopts it. Most Michigan data center ordinances treat a data center as a special land use: a use allowed only after a separate review against standards in the ordinance. MCL 125.3502 lets the ordinance require “supporting materials” with the application, which is the hook for requiring a sound study. MCL 125.3201 MCL 125.3401 MCL 125.3502
A general noise ordinance is a separate tool. It comes from the police power, not from zoning. In a general law township, the board acts under MCL 41.181. In a charter township, it acts under MCL 42.15. The board adopts it alone, with no planning commission hearing. MCL 41.181 MCL 42.15
-
Only a general ordinance reaches existing data centers.
A lawful use that existed before a zoning change may continue. That is a nonconforming use. A general ordinance has no such limit. In Natural Aggregates v. Brighton Township, the Court of Appeals held that a township could regulate an existing gravel mine under its general ordinance. So Section 3(b), which reaches existing data centers, belongs only in the general ordinance version. MCL 125.3208 Natural Aggregates
-
Use one method in both ordinances.
If the zoning text and the general ordinance use different metrics or limits, a facility can pass zoning review and violate the general ordinance on its first night, or the reverse. Use one metric, one measurement method, and one set of definitions in both. The weakest choice is a zoning clause that only says “shall comply with the township noise ordinance” when that ordinance has no number.
-
Put the number in the ordinance, not only in a condition.
Under MCL 125.3504, special land use standards “shall be specified in the zoning ordinance,” and a condition must be “necessary to insure compliance with those standards.” A numeric limit in the data center section gives later conditions, such as monitoring or generator hours, something to attach to. Recorded conditions change only by mutual consent, so they can run for the life of the use. MCL 125.3504
-
Do not totally exclude the use.
MCL 125.3207 says a zoning ordinance “shall not have the effect of totally prohibiting the establishment of a land use” where there is demonstrated need, unless no location in the township is appropriate. A very low limit that no site could meet invites that challenge. That is why the Most protective tier includes finding (7) in Section 1, which names where a compliant data center could go. MCL 125.3207
-
Financial guarantees cover mitigation, not review.
MCL 125.3505 authorizes a performance guarantee covering “the estimated cost of improvements” to “insure faithful completion of the improvements.” Barriers, enclosures, and silencers fit that grant. Testing and monitoring costs fit it less clearly. So Section 16(e) covers mitigation only. The attorney should confirm separate authority before requiring an escrow for acoustic review or testing under Section 10. MCL 125.3505
-
Enforcement tools.
A township board may make a violation a municipal civil infraction, a non-criminal violation that carries a civil fine. A zoning violation is also a nuisance per se, which means the township need only prove that the ordinance was violated, not that the noise was unreasonable in fact. Fine amounts depend on state law. MCL 41.183 MCL 42.21 MCL 125.3407
-
PA 233 does not cover data centers.
2023 PA 233 sets a state sound limit of 55 dBA, averaged over an hour, for large solar, wind, and storage facilities. It does not cover data centers. In May 2026 the Court of Appeals held that a compatible renewable energy ordinance may not be stricter than PA 233. That ruling does not reach data center ordinances. MCL 460.1222 MCL 460.1226 Court of Appeals, 2026
One caution follows. A data center campus may include a large battery plant or solar. If an ordinance writes one standard for “data centers and accessory energy facilities,” a covered energy part might fall under PA 233. Keep the data center standard separate, and state that PA 233 governs covered energy facilities to the extent it applies. Section 3(e) does this. MCL 460.1221
-
Effective dates differ by tool.
A zoning amendment takes effect seven days after notice of adoption is published, unless a later date is set. In a general law township, a general ordinance with a penalty takes effect 30 days after first publication. In a charter township, it takes effect on publication unless a later date is stated. Whether a pending application is subject to the new rules depends on state vested-rights law. MCL 125.3401 MCL 41.184 MCL 42.22
-
State the metric, and define where to measure.
In Tuscola Wind III v. Almer Charter Township, a limit of “45 decibels on the DBA scale” named no averaging period. The township won, but only after federal litigation over what its number meant. In Capitol Properties, an undefined measurement location left a business-zoned neighbor unprotected. Vague words used alone have failed, as in City of Grand Rapids v. Gasper. Measured octave-band limits in zoning have been upheld in Michigan since City of Rochester v. Superior Plastics in 1991. Tuscola Capitol Properties Gasper Rochester
-
Decide whether to allow waivers.
Section 2(l) treats a neighbor’s parcel as participating only if its owner signed a recorded agreement that expressly waives the sound limits. An ordinary utility or access easement does not count. A waiver lets a willing neighbor accept more sound, often for payment, but later buyers inherit the deal. The model leaves the choice to allow waivers at all to the township.
-
Confirm each standard’s edition.
The ordinance names technical standards for meters, measurement, modeling, tones, and vibration. Standards are revised. ISO 2631-2, for example, has a 2003 edition and a 2026 edition. Confirm the current edition of each before adoption, and decide whether to name a fixed edition or “the current edition.” IEC 61672-1 ISO 9613-2 ANSI S12.18 ISO 1996-2 ISO 2631-2:2003 ISO 2631-2:2026 ANSI S2.71
05 · What to ask an applicant
Ask for a survey before the application and a study with it.
The ordinance puts the cost of the studies on the applicant. Sound studies are technical and are prepared to win approval, so the township needs its own expert to check them. These are the items Appendix B requires, in plain terms.
Before the application: a background sound survey (Section 8)
- A survey plan, with locations and dates, that the township approves before the survey begins.
- A qualified acoustical consultant to run it. In Recommended and Most protective, the township’s reviewer may watch.
- At least two locations (Baseline) or three (Recommended and Most protective), facing the nearest neighbors with homes in each direction.
- At least 7 days of unattended monitoring in a row, including every night and a weekend. Most protective requires two such surveys in different seasons, one between November and March.
- Stored data at fine time steps, so the same record can produce the 10-minute, 15-minute, and 1-hour values each tier uses. The survey also logs wind, temperature, and rain, and records audio to identify sources.
- A public report giving the median hourly L90 for day and for night at each location. That is the background sound the cap in Section 4(c) uses.
With the application: a predictive sound study (Section 9)
- A study sealed or signed by a qualified acoustical consultant, using ISO 9613-2:2024 or an equivalent method the reviewer accepts. ISO 9613-2:2024
- Sound data from the maker of each specific machine proposed, by octave band, with all equipment at full load and fans at top allowed speed.
- Weather that carries sound toward every home, such as a clear, calm night, and a stated treatment of ground, buildings, barriers, and terrain.
- In Recommended and Most protective: a stated method for the two lowest bands (16 and 31.5 Hz), which ISO 9613-2 does not cover, and four operating cases. The cases are normal night operation, peak cooling on the hottest day, one generator test with its load bank, and all generators running in an emergency.
- Predicted dBA, dBC, and octave-band levels at each receptor point and on contour maps; a tone check; and the expected accuracy.
- A list of each mitigation measure the applicant commits to, with the sound level each must achieve. That list also sets the amount of the financial guarantee in Section 16(e).
- In Recommended and Most protective: the model input and output files, source data, and all assumptions. A reviewer cannot check a model without its inputs. FERC rule
- In Most protective: a run with hard ground (which reflects more sound) and a contour map out to 30 dBA.
Also ask for
- A generator testing plan that fits Section 7: the hours, how many generators run at once, the test length, and the yearly hour cap.
- An escrow deposit to pay the township’s reviewer (Section 10). In Recommended and Most protective, review is required. In Baseline it is optional.
06 · After construction
Test after each phase opens, and keep testing.
Every study is a prediction, so the ordinance checks the result with a meter. All measurements follow one procedure in Section 9(f): a Class 1 meter, the microphone 5 feet above the ground, no rain, limits on wind speed, and a certified record of what equipment was running. To separate the facility from other sound, the test compares readings with the facility on and off.
- Initial test. Within 90 days (Baseline) or 60 days (Recommended and Most protective) after each phase opens, a consultant measures at the receptor points used in the study, by day, at night, and during one generator test. In Recommended and Most protective, the final certificate of occupancy waits until this test shows compliance.
- Repeat tests. Recommended repeats the test every year for 5 years, during summer peak cooling. Most protective repeats it every year for the life of the use, with a summer test and a winter night test.
- Monitoring. Recommended requires at least one permanent monitoring station for the first 2 years of each phase, with monthly reports. Most protective requires a station in each direction with homes, for the life of the use, with data posted publicly within 24 hours. Baseline has no monitoring.
- Complaints. The operator keeps a contact line and logs each complaint. In Recommended, a consultant tests within 7 days of a detailed complaint, at the operator’s cost; in Most protective, within 72 hours. Ten or more complaints from three or more households in 6 months trigger a full test. A complaint alone never proves a violation; only a measurement does.
- Notice and cure. The zoning administrator gives written notice of a violation found by measurement. The operator then has 30 days to fix it, or up to a set longer period if new equipment is needed.
- Fines and stronger steps. Fines rise with repeat violations. In Recommended and Most protective, an uncured violation can lead to suspension of the approval for that phase after notice and a hearing. Most protective adds orders to reduce or stop named equipment, and revocation if the violation is not cured within a set period after suspension.
- Costs and the guarantee. When a test confirms a violation, the operator pays the township’s costs. In Recommended and Most protective, the township can draw on the financial guarantee to finish mitigation the operator fails to complete.
Expansions follow the same path. Before a new building, new outdoor equipment, louder replacement equipment, or a change in generator testing, the operator files an updated study (Section 15). Most protective also sets one sound budget for the site and any adjacent parcel under common control.
Read this before adopting
This is model text and research, not legal advice.
Bommarito Consulting prepared this ordinance as part of a research report. It has not been reviewed for any particular jurisdiction. State law, local charters, existing ordinances, and the facts of each site differ. A local attorney must review and adapt the text before a planning commission or board acts on it. Confirm the current edition of each standard, check state preemption, and confirm the authority for any escrow, guarantee, or condition.
The bracketed values are choices. The report explains the source of each number and marks the values that are its own judgment. Read the full report, especially Section 9 and Appendix B, before choosing.