Data center noise: has it been done, and can it be met?

What the science, the law, the engineering, and adopted local codes say about strict noise limits for data centers.

Michael Bommarito · November 24, 2026 · Research guide

The question

Strict data center noise rules have been adopted many times. The strictest have not yet been proven in operation.

Local governments writing data center rules often hear that strict noise limits “have never been done” or cannot be met. Our report checks that claim against the science, the law, the engineering, and the codes that local governments have adopted. The first part of the claim is not accurate. The second part has some force, and this page explains where.

This page summarizes Noise and Vibration Rules for Data Centers (version 1.0). The report rests on 890 source records and is current through November 24, 2026. Counts of adopted rules are a floor, not a census. The report is research, not legal advice.

30+Local governments outside Michigan with data center noise rules that set numeric limits, testing schedules, or both.
9Michigan local governments with numeric data center sound limits: eight confirmed from adopted or final-reading text, one more reported.
10States with sound limits for wind, solar, or storage siting. No state sets a numeric limit for data centers.
45–60 dBATypical adopted night limits outside Michigan. Michigan’s adopted continuous limits go as low as 40 decibels.
55 dBAMichigan’s PA 233 limit for large solar, wind, and storage. It does not cover data centers.
20 dBA gap this large between C-weighted and A-weighted levels marked all but one problem site in a peer-reviewed study of low-frequency complaints.

01 · The short answer

It has been done. The hard part is the lowest limits.

By November 2026, at least 30 local governments outside Michigan had adopted data center noise rules with numeric limits, testing schedules, or both. In Michigan, nine local governments had data center zoning with numeric sound limits. Eight are confirmed from adopted or final-reading text, and one more is reported in the news. Their fixed continuous limits run from 40 to 60 decibels. A 2025 consent judgment also set a court-ordered limit for one project in Saline Township. Pittsfield ordinance Wixom ordinance Saline consent judgment

The tools behind these rules are old. Octave-band limits cap sound in each slice of the frequency range. They appear in the industrial zoning standards Chicago commissioned in the 1950s, described in a 1955 planning report. A Michigan court upheld octave-band zoning limits in 1991. Paired dBA and dBC limits date to 2003 in Hilliard, Ohio. ASPO, 1955 Rochester v. Superior Plastics Hilliard code

The objection that strict limits are hard to meet has real force. Sound studies filed by applicants predict about 45 dBA at nearby homes for several designs that use ordinary measures. But a 45 dBA limit with a 3 dB modeling margin needs a design that models at about 42 dBA. Only one study with night results reached that. No study we reviewed shows 40 dBA at every home at night. And no published measurement after construction in the United States yet confirms any of these predictions.

The claim, checked

“This has never been done” is not accurate. Numeric data center noise rules are in force in dozens of local governments, including nine in Michigan. Their tools have been used in zoning for decades.

The fair concession is narrower. These rules are proven in adoption, not yet in court or in long-term operation. We found no court decision on any data center noise limit and no enforcement history for any Michigan data center noise provision.

The report’s other main findings follow. Each is covered in a section below.

  • Federal law leaves this job to local governments. No federal law sets or preempts noise limits for data centers.
  • States supply benchmarks, not data center limits. Ten states set limits for wind, solar, or storage. West Virginia now bars local noise rules for certified data centers.
  • Sleep and annoyance carry the health case. Heart disease effects are small per person, and infrasound health claims are not supported.
  • A-weighted limits alone miss the hum people complain about. A complete rule adds a low-frequency limit and a penalty for tones.
  • The method matters more than the number. Two rules that both say “50 dBA” can differ by 10 dB or more.
  • A three-tier menu fits different places. We offer night limits of 50, 45, and 40 dBA, each with low-frequency limits, a tonal penalty, testing, and enforcement.

02 · How sound is measured

A decibel number means little until you know how it was measured.

Decibels do not add like ordinary numbers.

A decibel (dB) is the unit of sound level. The scale is logarithmic. Each 10 dB step means ten times the acoustic energy. To an average listener, a 10 dB increase sounds about twice as loud. A 3 dB increase doubles the energy but is barely perceptible. Caltrans, Table 2-10 FTA manual

Two equal sources add 3 dB, not double the number. Two buses that each produce 70 dB together produce 73 dB. Ten equal sources add 10 dB. So 100 equal chillers are about 20 dB louder at a distance than one, and quieting a few of many units does little. Distance helps: sound from a compact source, called a point source, drops about 6 dB each time the distance doubles. Real sites add losses from the ground, the air, and barriers, and sometimes gains from weather. FTA manual Caltrans

Decibel ladder

60Heavy traffic at 300 ft · large business office
55Michigan’s PA 233 limit · Baseline tier day limit · WHO 1999 level for serious daytime annoyance
50Quiet urban daytime · dishwasher in the next room · Baseline tier night limit
45Recommended tier night limit · WHO 1999 value outside a bedroom at night
40Quiet urban nighttime · Most protective tier night limit · WHO 2009 night guideline
35The report’s floor: no penalty or cap sets an effective limit below this
30–40Quiet suburban nighttime · library
20–30Quiet rural nighttime · bedroom at night
Levels in dBA. Everyday examples are typical positions from a Caltrans chart, not measurements of any site. Actual rural night background depends on roads, wind, insects, frogs, and season, so an ordinance that relies on background should require a measurement at the site. WHO values use different time periods than the tier limits; see section 03. Caltrans, Table 2-5

dBA and dBC: the low-frequency hum.

A sound meter applies a filter called a frequency weighting. An A-weighted level (dBA) filters sound roughly the way human hearing does at moderate levels. It discounts low-pitched sound on purpose. Under A-weighting, a 50 Hz hum must be about 30 dB stronger than a 1,000 Hz sound to register as equally loud. A C-weighted level (dBC) counts that hum more fully. Pumps, large fans, compressors, and electrical equipment are typical sources of low-frequency sound, and data centers have all of them. FTA manual Institute of Acoustics

The gap between a sound’s dBC and dBA readings shows how much low-frequency energy it carries. ANSI and WHO use a gap of 10 dB as a trigger for a closer look. In a peer-reviewed study of residential complaints near industrial sources, the gap was more than 20 dB at all of the problem sites but one, which measured 19 dB. The same study shows the screen’s limits: one compressor station had a gap of only 13 dB, and the resident moved away to escape the noise. A gap test is a trigger to look closer, not a limit by itself. ANSI S12.9 Part 4 WHO 1999 Hessler, 2004

Leq and L90: the average and the quiet floor.

Sound changes from moment to moment, so a rule must say how to turn an hour of sound into one number. The equivalent sound level (Leq) is the steady level that carries the same energy as the changing sound over a stated period. Loud moments count heavily. The maximum level (Lmax) is the single loudest moment. The L90 is the level the sound stays above 90 percent of the time. It describes the quiet floor between events and is commonly used for background sound. FTA manual ANSI S12.100

The report gives a made-up example. Picture an hour at a home that is quiet at 35 dBA for 57 minutes, with one 3-minute event at 70 dBA, such as a generator start. That hour has an Leq of 57, an Lmax of 70, and an L90 of 35. The same hour of sound can produce numbers 20 dB apart depending on the metric. A 24-hour average can also hide the night. A source that runs at a steady 50 dBA day and night has a day-night level (Ldn) of about 56.4 dBA, because Ldn adds 10 dB to night hours.

Tones get a penalty.

A tonal sound has a clear pitch, heard as a whine or hum. Tones annoy people more than broadband sound at the same level. The American standard for predicting community annoyance, ANSI S12.9 Part 4, adds 5 dB to the measured level of a sound with a prominent tone. Three test methods exist for deciding whether a tone is prominent. Each has limits at low frequency, which is where data center tones often occur. ANSI S12.9 Part 4

Why two “50 dBA” rules can differ by 10 dB or more.

A rule must say what is measured, with which weighting, over what period, and where. Leaving any of these open moves the reading. Stafford County, Virginia’s 55 dBA applies at the project boundary, drops to 52 with a tone, and is tested every summer for 10 years. Linn County, Iowa’s 55 dBA is an hourly average at the wall of a home on adjacent residential land, and neighbors may waive it. Port Washington, Wisconsin’s “70 decibels” states no weighting, time basis, or test. Before comparing numbers, check the weighting, the time basis, the measurement point, and the testing schedule. Stafford ordinance Linn ordinance Port Washington code

Measurement details matter most on quiet rural nights. Caltrans measured about 45 dBA of wind noise on a microphone with a windscreen at about 11 mph. Wind at that speed would already exceed a 40 dBA night limit. A rural rule needs a lower wind limit and a statement that readings taken outside the limits must be repeated. Caltrans

03 · Health and environment

Sleep and annoyance carry the health case.

The most consistent evidence concerns sleep disturbance and annoyance. Both show clear exposure–response relationships across many studies. An exposure–response relationship is a curve that shows how the share of people affected changes as the sound level rises. Both effects are worse at night, for tonal and low-frequency sound, and in quiet places. That describes a data center in a rural township. Basner & McGuire, 2018 Guski et al., 2017

The curves have no sharp line where harm begins. The World Health Organization (WHO) estimates that about 2% of people are highly sleep-disturbed by road traffic at 40 dB at night, rising to 4.2% at 50 dB and 12.0% at 65 dB. Any limit chosen from such a curve is a judgment about how many affected people are acceptable. WHO 2018

There is no WHO number for data centers.

WHO’s 2018 guidelines do not cover industrial noise. A data center is an industrial source, so it is not accurate to say that WHO recommends a particular level for data centers. What a township can say accurately is narrower. WHO’s night values for transport sources range from 40 to 45 dB outdoors. Its 2009 night guideline is 40 dB, the lowest outdoor level at which WHO saw adverse effects. Its 1999 guidelines set 30 dB inside a bedroom and 45 dB outside a bedroom at night. WHO set the 45 dB value so people can sleep with windows open, assuming the window cuts sound by 15 dB. WHO 2018 WHO 2009 WHO 1999

Applying any of these values to a data center is reasoning by analogy. The analogy is reasonable, but it is a policy choice, not a medical finding. A township that says so plainly will be harder to challenge than one that overstates the science.

Heart disease and infrasound are weak grounds for a limit.

WHO rated the evidence linking road traffic noise to ischemic heart disease as high quality, with a relative risk of 1.08 for each 10 dB. The largest recent review pooled 20 studies of more than 8.4 million people. It found a smaller estimate of 1.017, with a range of uncertainty that includes no effect. Per person, the added heart risk from 10 dB more noise is a few percent at most. For one facility next to a few dozen homes, that is a weak basis for a specific limit. WHO 2018 Pershagen et al., 2025

Infrasound is sound below 20 Hz, the usual lower limit of hearing. Government studies in Canada and Finland found no support for the claim that turbine infrasound causes disease. In the Finnish test, people who blamed their symptoms on infrasound could not detect it, and its presence made no difference to how annoying they found the sound. Data center equipment is dominated by fans, chillers, and transformer hum, which sit mostly in the audible range. The infrasound findings should not be used to dismiss data center complaints, which concern audible sound. Nor should infrasound claims be used to inflate them. Health Canada study Finnish study

We found no medical study of people living near a data center or a cryptocurrency mine. The reports of symptoms near a large bitcoin mine in Texas come from news reporting and lawsuits, not medical research.

A township should therefore ground its limits in sleep and annoyance, not in heart disease or infrasound. Michigan’s nonpartisan Citizens Research Council judged several common concerns about data centers overstated. It still concluded that “the most concerning negative impact of data centers is noise pollution.” Citizens Research Council

04 · Engineering

Where the sound comes from, and what design can remove.

Data center sound comes from three groups of equipment. Cooling runs all the time: air-cooled chillers, cooling towers, dry coolers, and rooftop exhaust fans. Electrical equipment runs all the time: transformers hum at twice the line frequency, which is 120 Hz in North America. Backup generators run rarely but loudly, for outages and tests. The scale sets data centers apart. Virginia’s legislative auditors found that the average data center site in Virginia has 54 permitted generators. Smithfield study JLARC, 2024

Distance removes the hiss, not the hum.

Air absorbs high pitches far more than low ones. Over one mile, air removes about 6 dB at 1,000 Hz and almost nothing at 63 Hz. On clear, calm nights, the ground cools and sound bends back down toward homes. Walls and silencers also work best at high pitches. In one Coal City, Illinois design, chiller silencers gave 10 dB at 63 Hz but 39 dB at 1,000 to 2,000 Hz. So a data center that meets a 55 dBA limit can still be the loudest sound at a rural home at night, and its tones can be heard indoors. ISO 9613-2:1996 Coal City study

Prince William County, Virginia’s acoustics consultant measured in the Great Oak neighborhood, near an operating data center campus. The consultant could not separate the data center from traffic with a single spot reading. The consultant found a 55 Hz tone at all times at all locations, averaging about 51 dB outdoors, and estimated it at about 39 dB indoors, “likely audible indoors.” County consultant report

Complaints also arise below common limits. Virginia’s legislative auditors found that data center noise prompting resident complaints ranged from an estimated 40 to 59 decibels. That is “typically below the 55 or 60 decibel limit” that the large Northern Virginia counties allow. Those figures are total sound at the complainant’s location, not the data center alone. JLARC, 2024

Try the arithmetic

Adding units and moving away.

This uses the two rules of thumb the report states. Equal sources add on an energy basis: N identical units are 10 × log₁₀(N) dB louder than one. A point source drops about 6 dB per doubling of distance: the change is 20 × log₁₀(d₁ ÷ d₂) dB.

51 dBA at the home, from spreading alone (+0 dB for 1 unit; −24 dB for distance).

The default matches the report’s worked example: a point source at 75 dB at 50 feet is about 51 dB at 800 feet. This count of spreading alone is a ceiling check, not a prediction. Ground, air, buildings, and barriers lower real results; night inversions can raise them by several decibels at a distance. A roof full of chillers behaves more like an area than a point, so sound falls off more slowly close in. Neither rule accounts for tones or low-frequency content. A real study uses ISO 9613-2 in octave bands.

Applicant studies predict about 45 dBA at homes.

The report collected the sound studies that applicants filed to win approval. Several designs reach about 45 dBA at homes a few hundred feet to a mile away using ordinary measures. Some miss. Every result in the table below is a prediction made before construction. Consultants use different assumptions, so the results are not directly comparable.

Predicted levels at homes in applicant studies (models, not measurements)
ProjectMain mitigationPredicted result
Coal City, Illinois (2026) sourceDischarge silencers, intake louvers, barriers, generator silencersMaximum 41 dBA against a 44 dBA night limit
T5, Chantilly, Virginia (2026) sourceSilencers, louvers, compressor wraps62 dBA cut to 45 dBA; 57 dBC remains
Smithfield Gateway, Pennsylvania (2026) source20-foot chiller screen, terrain38–47 dBA at night
Chantilly Premier, Virginia (2023) sourceUpgraded fans, air handler silencers40–42 dBA by day (no night results)
Minooka, Illinois (2025) sourceTreatment on half of 336 chillers, 6-meter walls45–46 dBA against a 44 dBA night limit; background already 46 dBA
Raylan, Kentucky (2026) sourceRemote siting, 3,200–5,700 feet from homes45–49 dBA; up to 67 dBC
Sentinel Green Fig, Pennsylvania (2026) sourceLow-speed chillers, roof barriers49–54 dBA at the north homes

Low-frequency limits are where designs run out of room. C-weighted levels run 8 to 15 dB above A-weighted levels in the studies and resident data. Most modeled designs stay below 60 dBC, but Raylan predicts up to 67 dBC about a mile from homes. Smithfield study Raylan study

No U.S. measurement after construction yet confirms these predictions.

We found no published post-construction measurement in the United States showing a large operating data center at 45 dBA or less at homes, or confirming any of the modeled results. The closest case is abroad. A 2025 verification report for a Microsoft data center near Sydney, Australia could not measure the facility at nearby homes, because it was too quiet to separate from background sound there. The consultants measured the equipment near the source instead. From those readings they calculated about 30 and 32 dBA at two receiver locations, against limits of 36 and 50 dBA. Those receiver figures are calculations, not direct measurements. Sydney verification report

At the Tanner Way campus near Great Oak, low-frequency tones remained after a fan retrofit. A 2026 review of U.S. evidence found that “calibrated, standards-grade acoustic data remain scarce.” County consultant report Bray & Dominici, 2026

Design choices made early matter most.

Acoustic consultants describe the same order of preference: siting and setbacks, then equipment selection, then treatment at the source, then barriers, then operating rules, then verification. Quiet equipment is usually the largest and cheapest gain. Operators told Virginia’s auditors that “reducing noise after a building is operational can be difficult and expensive.” No operator has published a total noise mitigation cost for a facility. Acentech guide JLARC, 2024

Liquid cooling is not a noise cure by itself. It mainly removes indoor fans. The heat still leaves the site through outdoor dry coolers, towers, or chillers. We found no source that measures the change in noise at neighbors’ homes from switching to liquid cooling. An ordinance should therefore regulate sound at the home, not the cooling technology. DOE best practices

05 · The law

Federal law leaves noise to states and local governments.

The Noise Control Act of 1972 says that “primary responsibility for control of noise rests with State and local governments.” The Environmental Protection Agency (EPA) ran a noise office that trained local officials and wrote a model ordinance. Federal funding for that office ended in 1981 and 1982. The Act was never repealed. No federal law sets or preempts noise limits for data centers. A township that writes a data center noise rule is doing the job Congress assigned to it. 42 U.S.C. § 4901 Shapiro, 1991

No state sets a data center limit.

In 38 states, we found no general statewide numeric limit for fixed sources such as factories, substations, or data centers. Ten states have written sound limits for wind, solar, or storage siting. For a neighbor’s home at night, six of them set limits between 39 and 45 dBA. New York, Wisconsin, and North Dakota use 45, and Vermont uses 39. New Hampshire and Ohio use 40 or background plus 5, whichever is greater. These are the closest thing to a state-tested number for large outdoor equipment near homes. A drafter who borrows one should copy the metric, the time period, and the measurement point along with the number. New York rule Wisconsin rule North Dakota rule Vermont rule New Hampshire rule Ohio rule

Some states have acted on data centers without setting a number. Virginia and California now require a sound estimate before local approval, for facilities of 100 and 10 megawatts respectively. West Virginia went the other way. Since 2025 it has barred county and municipal noise ordinances for certified data centers. Each local government should check its own state’s law before drafting. Va. Code § 15.2-2209.5 California AB 1577 West Virginia HB 2014

Michigan: PA 233 sets 55 dBA, but not for data centers.

Michigan’s Public Act 233 of 2023 (PA 233) sets one state number: 55 dBA, averaged over an hour and modeled at the outer wall of a neighbor’s home. It covers solar of 50 megawatts or more, wind of 100 megawatts or more, and storage of 50 megawatts and 200 megawatt-hours or more. The Michigan Public Service Commission added a 5 dB tonal penalty to the models. It did so over a utility’s objection, noting that transformer and inverter sound is “typically tonal.” MCL 460.1226 MCL 460.1222 MPSC order, 2024

A data center is not a solar, wind, or storage facility, so PA 233 does not limit a township’s sound standard for one. The 2026 Court of Appeals ruling that limits local energy ordinances under PA 233 does not reach data center ordinances either. One caution follows. A campus may include a large battery plant or on-site solar. Drafters should keep the data center standard separate and state that PA 233 governs covered energy facilities to the extent it applies. MCL 460.1222 Court of Appeals, 2026

Michigan townships already hold the zoning power.

Under the Michigan Zoning Enabling Act, the planning commission drafts zoning text, holds a public hearing, and sends its recommendation to the township board. The board adopts it. Through that process, a planning commission can make a data center a special land use and set numeric sound limits as approval standards. It can require a background survey and an acoustic model with the application. It can also authorize conditions for testing, monitoring, and generator hours. The board separately controls the township’s general noise ordinance, which can reach existing sources that zoning cannot. MCL 125.3401 MCL 125.3504

The zoning power has one outer limit. MCL 125.3207 bars zoning that has “the effect of totally prohibiting” a use where there is demonstrated need, unless no appropriate location exists in the township. A township choosing very strict limits should show in its findings where a compliant data center could locate. MCL 125.3207

Courts uphold measured limits and strike vague words.

Courts have upheld noise limits that state what is measured, where, and how. They have struck vague words such as “disturbing” when used alone. In one Michigan case, a township limit of “45 decibels on the DBA scale” named no averaging period, and the dispute over its meaning reached federal court. The township won, but only after litigation that a stated metric would have avoided. Rochester v. Superior Plastics Grand Rapids v. Gasper Tuscola Wind III v. Almer

Neighbors began filing nuisance suits against data centers in 2026. These are allegations. None had a ruling on the merits in our sources. A nuisance suit is slow and costly, and it arrives after the facility is built. Compliance with a local ordinance “is generally not a complete defense.” WilmerHale, 2026

06 · What local governments have adopted

Dozens of places have written numeric rules.

The survey coded provisions for about 59 local governments in 23 states outside Michigan. Outside Michigan, adopted daytime limits at or near homes fall between 50 and 65 dBA in nearly all rules. Night limits run from 45 to 60 dBA. The most common value is 55 dBA. Chandler, Arizona adopted the earliest data center noise rule in the survey in December 2022. It bars the facility from exceeding the ambient levels observed in a baseline study at the nearest residential property line. Chandler ordinance

Linn County, Iowa

55 dBA and 65 dBC as hourly averages at the wall of a home on adjacent residential land. Tested at the end of construction, then every 5 years. Linn ordinance

Oglethorpe County, Georgia

55 dBA by day and 45 at night, with 65 and 55 dBC, at any property line. Tested within 90 days of each phase and on complaint. Oglethorpe ordinance

Stafford County, Virginia

55 dBA at the project boundary, 52 with a prominent tone. Tested within 90 days, then every summer for 10 years at peak cooling. Stafford ordinance

Augusta-Richmond County, Georgia

65 dBA by day and 60 at night as 15-minute averages, with a 5 dB tonal adjustment. Retested every 3 years, after an expansion, and after 10 complaints in 6 months. Augusta code

Some places are having second thoughts. In October 2026, the Prince William County, Virginia board voted to revive the stricter version of its 2025 rule that its consultants first proposed. Prince William Times

In Michigan, nine local governments have numeric limits.

Michigan’s adopted continuous limits range from 40 to 60 decibels. Several set 40 dBA at night. A few examples show both the range and the drafting problems.

  • Pittsfield Charter Township (October 2026): 50 dBA at the property line at all times and 40 at night next to homes. It adds 65 dBC at all times and 55 at night next to homes, caps the gap between dBC and dBA at 20 dB, and adds a 5 dB tonal penalty. Its text states “Leq” without an averaging period. Pittsfield ordinance
  • City of Wixom (August 2026): hourly averages of 55 dBA by day and 45 at night, with 70 and 60 dBC and a 10 dB tonal penalty. Where ambient is lower, the limit is ambient plus 1 dB. It is the only adopted Michigan text with both dBA and dBC hourly limits by day and night. Wixom ordinance
  • Clark Township (August 2026): the lower of 45 dBA or ambient L90 plus 5 by day, and of 40 or L90 plus 5 at night, with a 65 dBC cap. Clark Township ordinance
  • Saginaw Charter Township (November 2026): 40 “decibels” at the property line, day or night. That ties for the lowest adopted continuous limit. But the text names no weighting and no averaging period, and it has no low-frequency limit. Saginaw Charter Township ordinance

Two adopted Michigan ordinances and the Saline Township consent judgment still say only “decibels.” The Saline judgment sets 55 dB “at all times” at all property lines. It binds one project by court order and is not a township ordinance. Saline consent judgment

Common drafting errors.

Three errors matter most for a first rule. The first is a missing weighting or time basis, which can move a reading by 10 dB or more. The second is a clause that names a tool but sets no number. The Michigan Townships Association sample says octave bands “will be maintained at acceptable levels,” which gives an inspector nothing to measure. The third is a copied error. A standard cited as “ANSI S1.4-2104,” which does not exist, appears in more than one Pennsylvania text. MTA sample ordinance Lower Saucon ordinance

07 · Three tiers

A menu of limits for different places.

The report offers three tiers: Baseline, Recommended, and Most protective. They are a menu, not a ranking. A township next to an interstate and a township of quiet farms face different facts. The right tier depends on the measured background sound at night, the distance to homes, and how much risk the community will accept.

All three tiers share some definitions. Day runs from 7 a.m. to 10 p.m. and night from 10 p.m. to 7 a.m. Limits apply to the sound the facility contributes, not to total sound. They apply at any parcel the operator does not own or lease, unless its owner has signed a recorded agreement that expressly waives the limits. All dBA and dBC limits are Leq values measured 5 feet above grade.

The three tiers compared
ElementBaselineRecommendedMost protective
Where it fitsLoud settings, such as next to a highway or in an industrial park.Most places with homes within about a mile.Quiet rural places with close homes. It may rule out some sites.
Night limit (10 p.m.–7 a.m.)50 dBA45 dBA40 dBA
Day limit (7 a.m.–10 p.m.)55 dBA50 dBA45 dBA
Low-frequency (dBC) limit70 dBC day, 65 night. A gap of more than 10 dB between dBC and dBA requires a closer analysis.65 dBC day, 60 night. The gap may be no more than 20 dB.60 dBC day, 55 night. The gap may be no more than 20 dB.
Octave-band limitsBands from 16 to 8,000 Hz reported in tests, with no limit.65 dB at 16, 31.5, and 63 Hz, at all hours.A full table from 16 to 8,000 Hz, never above 65 dB.
Tonal penalty5 dB, named test.5 dB, named test, presumed in models unless disproven; a tone-free design avoids it.10 dB, with the same test.
Background capNone. Background is reported.At night, the lower of the limit or L90 + 10 dBA.At all hours, the lower of the limit or ANS-weighted L90 + 5 dBA.
FloorNo cap or penalty sets an effective limit below 35 dBA.Same.Same.
Averaging period1-hour Leq15-minute Leq10-minute Leq
Modeling marginNone.The model must meet each limit by 3 dB.Same as Recommended.
Night design target50 dBA, or 45 with a prominent tone (our arithmetic).About 42 dBA, or about 37 with a prominent tone.About 37 dBA, or about 32 with a prominent tone.
Independent reviewOptional, at the applicant’s cost.Required. The township picks the reviewer; the applicant funds an escrow.The reviewer also witnesses tests and audits data.
Test after constructionWithin 90 days of each phase.Within 60 days, then yearly for 5 years at summer peak.Yearly for the life of the use, on summer and winter nights.
Continuous monitoringNone.One or more stations for 2 years, with monthly reports.Permanent stations in each direction, with public data.
Generator testingWeekdays 8 a.m.–6 p.m.; 100 hours per generator a year (all tiers).Weekdays 9 a.m.–5 p.m.; one generator per building at a time.Weekdays 10 a.m.–4 p.m.; one on site at a time; 55 dBA during outages.

The 35 dBA floor, the survey location counts, the 2-year monitoring period, the complaint-response times, the cure periods, and the winter test are the report’s own judgment where no source sets a number. The Baseline night design target is our arithmetic from the table. The full report names the source for every other value, and the model ordinance puts each number in brackets so a drafter can choose.

Try the arithmetic

How the margin and the tonal penalty set the design target.

The effective night limit is the night limit minus any tonal penalty, but never below the 35 dBA floor. The design must then model below that effective limit by the tier’s margin.

Model at about 42 dBA at night: 45 dBA limit, no tonal penalty, minus a 3 dB margin.

Baseline: a floor, not a goal.

Baseline suits a site where the measured night background is already in the mid-40s or higher. Its 55 dBA day limit matches WHO’s 1999 threshold for serious annoyance outdoors and EPA’s 1974 outdoor level. Its 50 dBA night limit is the night value in the general state rules of Washington, New Jersey, Colorado, and Minnesota. Every applicant study the report reviewed predicts 54 dBA or less at homes, so a well-designed facility should meet this tier without unusual cost. But it will not prevent complaints, which arise at 40 to 59 dB. In a quiet rural township, Baseline is a weak rule. WHO 1999 EPA, 1974 JLARC, 2024

Recommended: the default for homes within about a mile.

The 45 dBA night limit equals WHO’s 1999 value outside a bedroom. WHO’s value is an 8-hour night average, so a 15-minute limit at 45 is stricter than WHO’s value at the same number. The 20 dB cap on the gap between dBC and dBA comes from the peer-reviewed low-frequency study. That study proposed the cap for very quiet sites with A-weighted limits below about 40 dB, so applying it with a 45 dBA limit is the report’s extension. The 3 dB modeling margin is the accuracy usually quoted for ISO 9613-2. WHO 1999 Hessler, 2004 Piercy, 1993

This tier is demanding. With the margin, a design must model at about 42 dBA at night. With a prominent tone, the 5 dB penalty applies too, and the design must model at about 37 dBA. Of the applicant studies, only Coal City, Illinois models at or below 42 at night. Chantilly Premier does too, but it reports daytime levels only. The tier is built to reward tone control. A design shown to have no prominent tone avoids the penalty and models against 42, not 37. Coal City study Chantilly Premier study

Most protective: for quiet rural places, with a record.

The 40 dBA night limit is WHO’s 2009 night guideline. This tier is at or beyond the edge of what the engineering record shows. No applicant study the report reviewed predicts 40 dBA at every home at night. A large air-cooled campus would probably need a setback on the order of a mile plus the full set of source treatments. Even distance alone is not enough: Raylan, Kentucky, 3,200 to 5,700 feet from homes, still models 45 to 49 dBA. A township choosing this tier should expect some sites to be unbuildable for a large air-cooled campus, say so in its findings, and show where a compliant facility could go. WHO 2009 Raylan study MCL 125.3207

The method matters more than the number.

A rule that states its metric, weighting, averaging period, and location will do more for neighbors than a lower number without them. So will a rule that requires independent studies before and after construction and names its measurement procedure. The report’s eight drafting principles apply to every tier:

  1. State the metric, weighting, averaging period, and location.
  2. Protect the night, with a night limit 5 dB below the day limit.
  3. Control low-frequency and tonal sound with numbers in the text.
  4. Tie limits to measured background where the place is quiet.
  5. Make the applicant pay for independent studies.
  6. Test after construction, and keep testing.
  7. Write an enforceable measurement procedure, including a Class 1 meter.
  8. Use one metric and one method in the zoning and general noise ordinances.

08 · Questions for an applicant

Ask for answers that can be checked.

These questions follow the report’s drafting principles and tier provisions. A planning commission, board, or resident can ask them about any proposal. Some answers belong in the application. Others should become conditions of approval.

  1. What exactly does your number measure?

    Ask the applicant to state the metric (such as Leq), the weighting (dBA or dBC), the averaging period, and the measurement location for every predicted level. A number without these four facts cannot be compared with a limit.

  2. What is the background at night, and how was it measured?

    Ask for a background survey of at least 7 days that includes a weekend, at 2 or more locations, with one-third-octave data. Ask which statistic sets the background. The report uses the L90 measured under ANSI/ASA S12.100.

  3. Can we check the model?

    Ask for the ISO 9613-2 model at full load, with octave bands from 63 to 8,000 Hz, dBA and dBC results, and the input files. Ask how the study handles the 16 and 31.5 Hz bands, which the standard does not cover.

  4. Does the design meet the limit with a margin?

    Ask whether each predicted level sits at least 3 dB below the limit. That is the accuracy usually quoted for ISO 9613-2. Ask what the model shows for homes more than about 500 meters away, where its accuracy is not demonstrated.

  5. Will the equipment make a prominent tone?

    Ask for a one-third-octave tonal assessment of chillers, fans, and transformers. Transformers hum at 120 Hz in North America. A design with no prominent tone avoids the tonal penalty.

  6. When and how will generators be tested?

    Ask for the test schedule, the number of units run at once, the hours, and whether load banks are covered. Load banks can be louder than the generator they serve.

  7. Who will prove the result after construction?

    Ask for a compliance test after each phase opens, retests at the loudest normal condition, and retests after complaints and expansions. Ask how the test will separate the facility from traffic and other sound.

  8. Who pays for the township’s own expert?

    Ask the applicant to fund an independent reviewer chosen by the township. In Michigan, MCL 125.3505 authorizes performance guarantees for “the estimated cost of improvements.” The township attorney should confirm separate authority before requiring an escrow for acoustic review or testing.

Sources for these questions: ANSI S12.100 (background) · ISO 9613-2:2024 (model bands) · Piercy, 1993 (accuracy) · ANSI S12.9 Part 4 (tones) · Chantilly Premier study (load banks) · Stafford ordinance (retests) · MCL 125.3505

A township that wants a rule can start with six steps from the report. Confirm the power and check for state preemption. Measure the background at night. Choose a tier and write down the reasons. Write the method into the text. Make the applicant pay for proof. Align the zoning and general noise ordinances. A local attorney should review the draft text before adoption, and a qualified acoustical consultant should review the technical standards.

Sources cited on this page

Read the original documents.

The sources include statutes, ordinances, court opinions, agency guidelines, peer-reviewed research, standards, and applicant sound studies. Each entry gives the date we last checked it. The full report cites 890 source records.

  1. Document
    Pittsfield Charter Township, Michigan: ZOA #26-236, Zoning Sec. 40-11.51 High Resource Demand Facilities (adopted)

    Pittsfield Charter Township · 2026-10-28 · Checked 2026-11-24

  2. Document
    City of Wixom, Michigan: Ordinance No. 2026-01, Zoning Sec. 18.09.040.N Data Centers (clean adopted text)

    City of Wixom · 2026-08-25 · Checked 2026-11-24

  3. Document
    Saline Township, Michigan: Consent Judgment, RD Michigan Property Owner I LLC et al. v. Saline Township, Washtenaw Cir. Ct. No. 2025-001577-CZ, para. 3(t) (site-specific, not an ordinance)

    Washtenaw County Circuit Court · 2025-10-15 · Checked 2026-11-24

  4. Report
    Industrial Zoning Standards

    American Society of Planning Officials · 1955-09 · Checked 2026-11-24

  5. Document
    City of Rochester v. Superior Plastics, Inc., 192 Mich App 273 (1991)

    Michigan Court of Appeals · 1991-12-27 · Checked 2026-11-24

  6. Law or ordinance
    Codified Ordinances, Sec. 531.03, Maximum Permissible Sound Levels

    City of Hilliard · 2003-05-12 · Checked 2026-11-24

  7. Report
    Technical Noise Supplement to the Traffic Noise Analysis Protocol

    California Department of Transportation · 2013-09 · Checked 2026-11-24

  8. Report
    Transit Noise and Vibration Impact Assessment Manual

    Federal Transit Administration · 2018-09 · Checked 2026-11-24

  9. Report
    Briefing Note: Low Frequency Noise (LFN) Annoyance

    Institute of Acoustics · 2024-01 · Checked 2026-11-24

  10. Report
    ANSI S12.9-2005/Part 4: Quantities and Procedures for Description and Measurement of Environmental Sound, Part 4: Noise Assessment and Prediction of Long-term Community Response

    Acoustical Society of America · 2005 · Checked 2026-11-24

  11. Report
    Guidelines for Community Noise

    Birgitta Berglund, Thomas Lindvall, and Dietrich H. Schwela · 1999 · Checked 2026-11-24

  12. Research article
    Proposed Criteria in Residential Communities for Low-Frequency Noise Emissions from Industrial Sources

    George F. Hessler · 2004 · Checked 2026-11-24

  13. Web page
    ANSI/ASA S3/SC1.100-2014 / ANSI/ASA S12.100-2014: Methods to Define and Measure the Residual Sound in Protected Natural and Quiet Residential Areas

    Acoustical Society of America · 2014 · Checked 2026-11-24

  14. Law or ordinance
    Ordinance O25-29(R): An Ordinance to Amend and Reordain Stafford County Code Sec. 28-39, Special Regulations, Regarding Data Centers

    Stafford County Board of Supervisors · 2025-12-02 · Checked 2026-11-24

  15. Law or ordinance
    Ordinance 3-2-2026: EU-3 Large-Scale Data Center District

    Linn County Board of Supervisors · 2026-02-18 · Checked 2026-11-24

  16. Law or ordinance
    Port Washington Code, Sec. 485-172, I-3 Technology Campus District

    City of Port Washington · 2025-04-15 · Checked 2026-11-24

  17. Research article
    WHO Environmental Noise Guidelines for the European Region: A Systematic Review on Environmental Noise and Effects on Sleep

    Mathias Basner and Sarah McGuire · 2018 · Checked 2026-11-24

  18. Research article
    WHO Environmental Noise Guidelines for the European Region: A Systematic Review on Environmental Noise and Annoyance

    Rainer Guski, Dirk Schreckenberg, and Rudolf Schuemer · 2017 · Checked 2026-11-24

  19. Report
    Environmental Noise Guidelines for the European Region

    World Health Organization Regional Office for Europe · 2018 · Checked 2026-11-24

  20. Report
    Night Noise Guidelines for Europe

    World Health Organization Regional Office for Europe · 2009 · Checked 2026-11-24

  21. Research article
    Road Traffic Noise and Incident Ischemic Heart Disease, Myocardial Infarction, and Stroke: A Systematic Review and Meta-Analysis

    Göran Pershagen et al. · 2025 · Checked 2026-11-24

  22. Research article
    Exposure to Wind Turbine Noise: Perceptual Responses and Reported Health Effects

    David S. Michaud et al. · 2016 · Checked 2026-11-24

  23. Web page
    VTT Studied the Health Effects of Infrasound in Wind Turbine Noise in a Multidisciplinary Cooperation Study

    VTT Technical Research Centre of Finland · 2020-04-20 · Checked 2026-11-24

  24. Report
    Citizens Research Council of Michigan, Report 426: Data Centers in Michigan: Evaluation of Policy Controversies Regarding Hyperscale Data Center Development (June 2026)

    Citizens Research Council of Michigan · 2026-06-15 · Checked 2026-11-24

  25. Report
    Acoustical Evaluation of Sound Emissions, Smithfield Gateway Data Center Campus, Smithfield Township, PA (Rev. 1)

    Ostergaard Acoustical Associates for Legend Properties (filed with Smithfield Township) · 2026-08-10 · Checked 2026-11-24

  26. Report
    Data Centers in Virginia 2024 (Report 598)

    Joint Legislative Audit and Review Commission, Virginia · 2024-12-09 · Checked 2026-11-24

  27. Report
    ISO 9613-2:1996, Acoustics: Attenuation of Sound During Propagation Outdoors, Part 2: General Method of Calculation

    International Organization for Standardization · 1996 · Checked 2026-11-24

  28. Report
    Project Heartland Environmental Noise Study (Aligned Data Centers, Coal City IL)

    WorkingBuildings / Cerami for Aligned Data Centers (posted by Village of Coal City) · 2026-07-20 · Checked 2026-11-24

  29. Report
    Great Oaks Sound Monitoring, Preliminary Report, Update v1.1

    David A. Nelson, Nelson Acoustics, for Prince William County DCOAG · 2025-05-07 · Checked 2026-11-24

  30. Report
    Raylan Data Center Noise Assessment Summary Report (KY PSC 2026-00115)

    ERM for Justified DataPower (Kentucky PSC filing) · 2026-08-25 · Checked 2026-11-24

  31. Report
    Microsoft SYD05 Data Centre Operational Noise Verification Report (Report 250792 R0), prepared for Microsoft Datacentre (Australia)

    Pulse White Noise Acoustics · 2025-12-17 · Checked 2026-11-24

  32. Web page
    Noise Emissions from Hyperscale AI Data Centers: A Poorly Characterized Exposure (arXiv:2610.03975; accepted, Noise & Health)

    Bray and Dominici · 2026-10-02 · Checked 2026-11-24

  33. Web page
    Good noise neighbor: Data center design for community noise

    Building Design + Construction (Alex Odom, Acentech) · 2026-01-02 · Checked 2026-11-24

  34. Report
    Best Practices Guide for Energy-Efficient Data Center Design (revised July 2024)

    U.S. Department of Energy, FEMP · 2024-07 · Checked 2026-11-24

  35. Document
    42 U.S.C. § 4901 (Noise Control Act of 1972, findings and policy)

    U.S. Congress · 1972 · Checked 2026-11-24

  36. Report
    The Dormant Noise Control Act and Options to Abate Noise Pollution

    Sidney A. Shapiro · 1991 · Checked 2026-11-24

  37. Document
    16 NYCRR § 1100-2.8, Exhibit 7: Noise and Vibration (Cornell LII copy)

    New York Office of Renewable Energy Siting and Electric Transmission · 2024 · Checked 2026-11-24

  38. Document
    Wis. Admin. Code PSC 128.14, Noise Criteria

    Wisconsin Legislature · 2026 · Checked 2026-11-24

  39. Document
    N.D. Admin. Code ch. 69-06-08, Energy Conversion Facility Siting Criteria

    North Dakota Legislative Branch · 2026 · Checked 2026-11-24

  40. Document
    Rule 5.700, Rule on Sound Levels from Wind Generation Facilities

    Vermont Public Utility Commission · 2017 · Checked 2026-11-24

  41. Document
    N.H. Code Admin. R. Site 301.14, Criteria Relative to Findings of Unreasonable Adverse Effects (Cornell LII copy)

    New Hampshire Site Evaluation Committee · 2026 · Checked 2026-11-24

  42. Document
    Ohio Adm. Code 4906-4-09, Regulations Associated with Wind and Solar Facilities

    Ohio Power Siting Board · 2024 · Checked 2026-11-24

  43. Document
    Va. Code § 15.2-2209.5, Siting of Data Centers; Site Assessment (2026 Acts cc. 567, 568)

    Virginia General Assembly · 2026 · Checked 2026-11-24

  44. Document
    AB 1577 (2025–26), Data Centers: Reporting, Chapter 434, Statutes of 2026

    California Legislature · 2026 · Checked 2026-11-24

  45. Document
    Enrolled Committee Substitute for House Bill 2014 (2025), Adding W. Va. Code § 5B-2-21b; Approved by the Governor April 30, 2025

    West Virginia Legislature · 2025 · Checked 2026-11-24

  46. Document
    MCL 460.1226, PA 233 contested case and facility standards (sound standard at (8)(a)(iv), (8)(b)(iv), (8)(c)(iii))

    Michigan Legislature · 2023 · Checked 2026-10-07
    Copy retained from an earlier Bommarito Consulting project.

  47. Document
    MCL 460.1222, PA 233 applicability thresholds

    Michigan Legislature · 2023 · Checked 2026-10-07
    Copy retained from an earlier Bommarito Consulting project.

  48. Document
    MPSC Case U-21547, Order of October 10, 2024 implementing PA 233 (Sound Modeling Guidelines discussion, pp. 65-71)

    Michigan Public Service Commission · 2024-10-10 · Checked 2026-10-07
    Copy retained from an earlier Bommarito Consulting project; re-read 2026-11-24.

  49. Document
    In re Implementing Provisions of Public Act 233 of 2023, Mich. Ct. App. No. 373259 (May 7, 2026, published; amended May 14, 2026)

    Michigan Court of Appeals · 2026-05-07 · Checked 2026-10-07
    Copy retained from an earlier Bommarito Consulting project; re-read 2026-11-24.

  50. Document
    MCL 125.3401, Adoption of zoning ordinance and amendments by legislative body

    Michigan Legislature · 2006 · Checked 2026-11-24

  51. Document
    MCL 125.3504, Special land uses; standards; conditions; record of conditions

    Michigan Legislature · 2006 · Checked 2026-11-24

  52. Document
    MCL 125.3207, Zoning ordinance or decision; effect as prohibiting establishment of land use

    Michigan Legislature · 2006 · Checked 2026-11-24

  53. Document
    People of the City of Grand Rapids v. Gasper (consolidated with v. Smith and v. Lehnen), 314 Mich App 528 (2016)

    Michigan Court of Appeals · 2016-03-08 · Checked 2026-11-24

  54. Document
    Tuscola Wind III, LLC v. Almer Charter Township, No. 1:17-cv-10497, ECF No. 60 (E.D. Mich. Mar. 12, 2018)

    U.S. District Court for the Eastern District of Michigan · 2018-03-12 · Checked 2026-11-24

  55. Web page
    Data Centers in Court: The Emerging Wave of Nuisance, Environmental, and Land-Use Litigation

    WilmerHale · 2026-07-13 · Checked 2026-11-24

  56. Law or ordinance
    Ordinance No. 5033 (Data Centers), Amending Chandler City Code Chapter 35

    City of Chandler · 2022-12-08 · Checked 2026-11-24

  57. Law or ordinance
    Unified Development Code Amendment: Commercial Data Centers and Digital Computing Facilities (Sec. 713), Ready for Adoption

    Oglethorpe County · 2026-09 · Checked 2026-11-24

  58. Law or ordinance
    Final Draft Proposed Data Center Ordinance (Sec. 24-A)

    Augusta-Richmond County Planning and Development · 2026-09 · Checked 2026-11-24

  59. Web page
    County Supervisors Backtrack on Data Center Noise Ordinance

    Prince William Times · 2026-10-27 · Checked 2026-11-24

  60. Document
    Clark Township (Mackinac County), Michigan, Ordinance No. 2026-02, Data Centers (board-approved text of August 19, 2026; copy posted by the City of Negaunee)

    Clark Township · 2026-08-19 · Checked 2026-11-24

  61. Document
    Saginaw Charter Township, Michigan: Ordinance No. 814 (Z-26-06), Zoning Sec. 2226.5 data center standards ('Final with PC Changes 10-21-26' clean text in 11/9/26 board packet)

    Saginaw Charter Township · 2026-11-09 · Checked 2026-11-24

  62. Document
    Michigan Townships Association (sample ordinance), Michigan: Sample Data Center Ordinance Version 1.0, Secs. F (Sound) and H (Vibrations)

    Michigan Townships Association · 2026 · Checked 2026-11-24

  63. Law or ordinance
    Ordinance No. 2026-__: Data Centers, Chapter 180 Zoning

    Lower Saucon Township Council · 2026-05-20 · Checked 2026-11-24

  64. Report
    Information on Levels of Environmental Noise Requisite to Protect Public Health and Welfare with an Adequate Margin of Safety

    U.S. Environmental Protection Agency · 1974-03 · Checked 2026-11-24

  65. Research article
    The Draft International Standard Method (ISO/DIS 9613-2) for Calculating the Attenuation of Sound Outdoors

    J. Piercy · 1993 · Checked 2026-11-24

  66. Report
    Preliminary Sound Modeling Report, Chantilly Premier, Fairfax County, Virginia

    Ramboll for Kimley-Horn (posted by Fairfax County Sully District) · 2023-08-14 · Checked 2026-11-24

  67. Web page
    ISO 9613-2:2024, Acoustics: Attenuation of Sound During Propagation Outdoors, Part 2: Engineering Method for the Prediction of Sound Pressure Levels Outdoors

    International Organization for Standardization · 2024-01 · Checked 2026-11-24

  68. Document
    MCL 125.3505, Performance guarantee

    Michigan Legislature · 2006 · Checked 2026-11-24

  69. Report
    T5@Chantilly - Project Charlie Environmental Noise Study

    WorkingBuildings / Cerami for T5 (posted by FFXnow) · 2026-09-17 · Checked 2026-11-24

  70. Report
    Equinix Data Center - Acoustic Evaluation, Minooka IL

    Shen Milsom & Wilke for Equinix (posted by Village of Minooka) · 2025-09-03 · Checked 2026-11-24

  71. Report
    Acoustical Evaluation of Proposed Data Centers, Sentinel Green Fig, East Whiteland, Pennsylvania (letter report)

    Lewis S. Goodfriend & Associates for Sentinel Green Fig LLC (posted by East Whiteland Township) · 2026-02-19 · Checked 2026-11-24